Mascot LX Service Manual
Appendix 1 - SIT Parameter Codes (continued)
App1
cont.
INSTALLER MODE PARAMETERS
Parameter
Description
Default
P01
Service notification months
12
P02
Service notification hours since last service
8760
P03
Service notification cycles
500
P04
Timeout for service mode
180
P05
Modbus timeout
10 sec.
P06
Cascade address and configuration
1
P07
Cascade temperature set point
180°F
P08
Cascade temperature offset
10°F
P09
Cascade temperature hysteresis from offset
20°F
P10
Minimum power percentage before a cascade boiler is
switched off
30%
P11
Minimum time a bic must remain on or off
30 sec.
P12
Minimum next on time
60 sec.
P13
Maximum kBtu of this unit
125
P14
Maximum kBtu of Slave 1
0
P15
Maximum kBtu of Slave 2
0
P16
Maximum kBtu of Slave 3
0
P17
Maximum kBtu of Slave 4
0
P18
Maximum kBtu of Slave 5
0
P19
Maximum kBtu of Slave 6
0
P20
Maximum kBtu of Slave 7
0
P21
Power at which next boiler is switched on
90%
P22
Power at which next boiler is switched off
35%
P23
Anti short cycling time
30 sec.
P24
Anti cycling dropoff temperature on s2
10°F
P25
0 - 10V to Power (fan speed)
Enabled
P26
0 - 10V to outlet setpoint
Disabled
P27
Alarm contact configuration
Enabled
P28
Domestic hot water demand blocks system pump enable/
disable
Disabled
P29
System pump always on enable/ disable
Disabled
P30
0 - 10V input enable/ disable
Enabled
Содержание MASCOT LX
Страница 2: ......
Страница 6: ...Mascot LX Service Manual iv...
Страница 24: ...Mascot LX Service Manual 18...
Страница 38: ...32 Mascot LX Service Manual...
Страница 76: ...70 Mascot LX Service Manual...
Страница 90: ...84 Mascot LX Service Manual Appendix 3 Wiring Diagrams continued App3 cont Fig App3 2 120V Wiring Diagram...
Страница 93: ......