Mascot LX Service Manual
Condensate Trap
Some operating conditions can cause small particles
of mineral material to be formed in the heat exchanger
and collect in the condensate trap. The drain can also
be blocked if it is frozen or plugged with debris. If the
water cannot drain freely, it can back up into the heat
exchanger.
The trap on the Mascot LX has a removable cap, so it is
easy to clean. Remove the cap and flush out this area
at least once a year.
On a Mascot LX unit, the condensate trap is installed
outside of the cabinet, so it should be easy to reach. Note
that the condensate water can be hot. The water is also
acidic, and can damage metal pipes. The center of the
assembly includes a Nylon ball, which acts as a one-way
check valve. If you remove the threaded part at the bot-
tom of the assembly, be careful not to lose this ball.
Fig. B14-1 - Condensate trap assembly (typical)
Inlet -
from
boiler
Outlet to
drain
Remov-
able cap
for easy
cleanout
B14