Mascot LX Service Manual
B12
cont.
Air Pressure Switch (continued)
This switch acts as a “fan proving” switch. The switch
measures the difference in air pressure between the
Venturi and the flue collector.
Because the switch is normally open (N.O.), you should
see continuity across the switch contacts when the boiler
is running, and no continuity when it is off.
Fig. B12-1 - Air pressure switch