33
Mascot LX Service Manual
Troubleshooting the 120V AC Power Supply
Some of the components in the boiler operate on 120V AC, including . . .
• Boiler pump
• System pump
- and on “Combi” units (including Domestic Hot Water) -
• Domestic Hot Water pump
• Three-way valve
Figure B1-1 is a circuit diagram.
Some of the parts inside the power box can carry full line voltage. This voltage can
cause death or serious personal injury. Do not open this box or work inside unless
you have been trained in safe electrical service techniques.
Fig. B1-1 - 120V AC Power Distribution
Important note:
The maximum
combined load on
terminals PWB 4,
6, and 8 (the pump
outputs) must not
exceed 5 Amps.