INSTRUCTION MANUAL FOR PC63 CAGE 

Page 8 of 10 

 

POWER CABLING FORMULAS 

 

WIRE GAUGE TABLE 

 

 

SIZE 

AWG 

AREA 

CIR. 

MILS 

 

SIZE 

MCM* 

AREA 

CIR. 

MILS 

18 

1620 

250 

250000 

16 

2580 

300 

300000 

14 

4110 

350 

350000 

12 

6530 

400 

400000 

10 

10380 

500 

500000 

16510 

600 

600000 

26240 

700 

700000 

41740 

750 

750000 

52620 

800 

800000 

66360 

900 

900000 

83690 

1000 

1000000 

105600 

1250 

1250000 

00 

133100 

1500 

1500000 

000 

167800 

1750 

1750000 

0000 

211600 

2000 

2000000 

 
*Denotes all sizes larger than #0000 are expressed in MCM.

 

 
TABLE OF CONVENTIONS:
 

CMA

 

Cross-section of wire in circular MIL area. 

A

 

Ultimate drain in amperes. 

LF

 

Conductor loop feet. 

MAX AMP

 

Maximum allowable amperes for given voltage drop. 

CMA

 

Cross section of wire in circulate MIL area. 

AVD

 

Allowable voltage drop. 

LF

 

Conductor loop feet. 

K

 

11.1 Constant factor for commercial (TW Type) copper wire (KS5482-01). 

 

17.4 for aluminum (KS20189) 

 

 
1.  Calculating Wire Size Requirements..................................................CMA= A x LF x K 
 

 

 

 

 

 

 

 

 

      AVD 

 
2.  Calculating Current Carrying Capacity of Wire..........................Max Amp = CMA x AVD

 

 

 

 

 

 

 

 

 

 

     LF x K 

 
SOURCE:  HANDBOOK 100-NATIONAL BUREAU OF STANDARDS  

NOTE:  ALL WIRE #6 AND LARGER IS STRANDED.  

 

Содержание PC63 Series

Страница 1: ...OR PC63 CAGE Page 1 of 10 INSTRUCTION MANUAL FOR PC63 CAGE ECN DATE CPN106833 16816 6 05 106 BRADROCK DRIVE DES PLAINES IL 60018 847 299 1188 FAX 847 299 3061 ISSUE DATE 15689 12 02 INSTRUCTION DRAWIN...

Страница 2: ...THE INSTRUCTIONS EXACTLY To reduce risk of battery explosion follow these instructions and those published by the battery manufacturer and manufacturer of any equipment you intend to use in the vicin...

Страница 3: ...orrode and damage equipment A sealed maintenance free or valve regulated lead acid VRLA may be placed below this equipment Never allow the battery electrolyte to drip on this unit when reading the spe...

Страница 4: ...to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or equipment for handling Unti...

Страница 5: ...4V A63 24V A63 PC63 30 48V 130V 48V A63 48V A63 TPCD DISTRIBUTION CENTER PC63 60 24V 130V 24V A63 24V A63 TPCD DISTRIBUTION CENTER PC63 120 12V 130V 12V A63 12V A63 12V A63 12V A63 Input DC The A63 mo...

Страница 6: ...ept a TPCD connect the negative wire from the battery must be connected to the terminal marked negative and the positive wire from the battery must be connected to the terminal marked positive on the...

Страница 7: ...ENT CUSTOMER CONNECTION EQUIPMENT GROUNDING CONDUCTOR MINIMUM FUSE SIZE WIRE SIZE REQUIREMENT CUSTOMER CONNECTION EQUIPMENT GROUNDING CONDUCTOR MINIMUM 1 14 14 150 1 6 3 14 14 175 1 0 6 4 14 14 200 2...

Страница 8: ...enotes all sizes larger than 0000 are expressed in MCM TABLE OF CONVENTIONS CMA Cross section of wire in circular MIL area A Ultimate drain in amperes LF Conductor loop feet MAX AMP Maximum allowable...

Страница 9: ...ers and alarms for accuracy 4th Year REPEAT ABOVE WITH THE ADDITION OF 1 Check relay contacts for pitting or corrosion 2 Check capacitors for leakage 7th Year REPEAT ALL WITH THE ADDITION OF 1 Filter...

Страница 10: ...lity for proper installation installation adjustments and service arrangements Should minor adjustments be required the local La Marche Sales Representative should be contacted to provide this service...

Отзывы: