background image

3

SPECIFICATIONS

 Measuring Ranges and Accuracy (at 23

±5

, relative 

humidity75% or less)

AC Current 

 A

(RMS value detection) 

Maximum Input Current : 120A

Range

Display range

Allowable input

Accuracy

60A

0.00

60.39A

0.00

60.00Arms

(85Apeak or less)

±2.0%rdg±5dgt

(45

65Hz)

sine wave

120A

0.0

603.9A

0.0

120.0Arms

(170Apeak or less)

 For non-sinusoidal waveforms, add ±(2% of r 2% of 

full scale), for Crest factor<2.5.

DC Current 

 A 

Maximum Input Current : 120A

Range

Display range

Allowable input

Accuracy

60A ±0.00

60.39A

±0.00

60.00A

±2.0%rdg±8dgt

120A ±0.0

603.9A

±0.0

120.0A

±2.0%rdg±5dgt

AC Voltage 

 V

(RMS value detection, Auto-range) 

Maximum Input Voltage : 600V

Range

Display range

Allowable input

Accuracy

6V

0.000

6.039V

0.300

600.0Vrms

(850Vpeak or less)

±1.5%rdg±5dgt

(45

400Hz)

sine wave

60V

5.60

60.39V

600V

56.0

603.9V

Input Impedance

approx. 10M

Ω

 <200pF

 For non-sinusoidal waveforms, add ±(2% of r 2% of 

full scale), for Crest factor<2.5.

DC Voltage 

 V

(Auto-range) 

Maximum Input Voltage : 600V

Range

Display range

Allowable input

Accuracy

600mV ±0.0

603.9mV

±0.0m

600.0V

±1.0%rdg±3dgt

6V

±0.560

6.039V

60V

±5.60

60.39V

600V

±56.0

603.9V

Input Impedance

approx. 10M

Ω

Resistance 

Ω

  (Auto-range)

Range

Display range

Allowable input

Accuracy

600

Ω

0.0

603.9

Ω

0.0

Ω

60.00M

Ω

±1.0%rdg±5dgt

6k

Ω

0.560

6.039k

Ω

60k

Ω

5.60

60.39k

Ω

600k

Ω

56.0

603.9k

Ω

6M

Ω

0.560

6.039M

Ω

±2.0%rdg±5dgt

60M

Ω

5.60

60.39M

Ω

±3.0%rdg±5dgt

 Open-loop  Voltage

approx.0.6V, Measuring Current : 0.3mA or 

less

Continuity 

Range

Display range

Allowable input

Accuracy

600

Ω

0.0

603.9

Ω

0.0

600.0

Ω

±1.0%rdg±5dgt

The buzzer turns on for resistances lower than 35±25

Ω

.

 Open-loop  Voltage

approx.0.6V, Measuring Current : 0.3mA 

or less

Diode 

Range

Display range

Allowable input

Accuracy

2V

0.000

1.999V

0.000

1.999V

±3.0%rdg±5dgt

Open-loop Voltage

approx.2.7V

Capacitor 

 (Auto-range)

Range

Display range

Allowable input

Accuracy

40nF

0.00

40.39nF

the accuracy is not guaranteed

400nF

36.0

403.9nF

40.0n

40.00

μ

F ±2.5%rdg±10dgt

4

μ

F

0.360

4.039

μ

F

40

μ

F

3.60

40.39

μ

F

400

μ

F 36.0

403.9

μ

F

the accuracy is not guaranteed

4000

μ

F 360

4039

μ

F

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание KEW MATE 2012RA

Страница 1: ...DIGITAL MULTIMETER WITH AC DC CLAMP SENSOR KEW MATE 2012RA www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Страница 2: ...his instrument has been designed and tested according to IEC Publication 61010 Safety Requirements for Electronic Measuring Apparatus This instruction manual contains warnings and safety rules which m...

Страница 3: ...omes standard with the instrument Clamp sensor for ease of use in crowded cable areas and other tight places Permits current measurement with an open current clamp sensor that does not require opening...

Страница 4: ...Input Voltage 600V Range Display range Allowable input Accuracy 600mV 0 0 603 9mV 0 0m 600 0V 1 0 rdg 3dgt 6V 0 560 6 039V 60V 5 60 60 39V 600V 56 0 603 9V Input Impedance approx 10M Resistance Auto...

Страница 5: ...g System modulation Display Liquid crystal display Maximum Reading 6039 Except Hz 9999 CAP 4039 Diode 1999 Bar graph with maximum points of 30 Display approx 3 times per second Indication renewal Loca...

Страница 6: ...the batteries according to section 8 Battery Replacement NOTE When the instrument is left powered on the auto power save function automatically shut the power off The display blanks even if the Functi...

Страница 7: ...LCD 2 Adjust one of the conductors to the center of the clamp sensor s arrow When the position of the conductor is not at the center of the arrow the error occurs Measured value is shown on the displa...

Страница 8: ...urement DANGER In order to avoid possible shock hazard never make measurement on circuits with a maximum voltage difference of 600V or greater between conductors 300V or greater between a conductor an...

Страница 9: ...Turn the function switch to the OFF and then to any position 7 2 Data Hold Function This is a function to freeze a measured value on the display Press the Button once to hold the current reading In t...

Отзывы: