KEW6305
7.6
7.2 Survey closure
There are two ways of closing a survey.
(1) Manual operation
Pressing
START/STOP
key on
Wh
range for 2 sec. or more closes the survey. This action also
closes a survey started automatically at a preset time and date. LED status indicator goes off. The
survey is then closed.
(2) Automatic operation (presetting the time and date)
This can be done by presetting the stop time and date on
SET UP
range. LED status indicator
goes off. The survey is then closed.
NOTE
* A survey will be closed and lost when the instrument is switched off.
* Manually starting a survey renders a preset stop time and date ineffective. The survey has to be closed
manually in this case.
* If the survey duration is shorter than the integration interval (“
Setting 09
”) the measured data will not be
saved.
* If the preset start time and date come after the preset stop time and date, the survey cannot be done.
* Pressing the
START/STOP
key 2 sec. or more releases the stand-by mode.LED status indicator goes off.
7.3 Resetting the integration value
There are two methods for resetting the integration value and period from previous measurements.
a) Press
ESC
key on
Wh
range 2 sec. or more.
b) System reset
NOTE
* Integration value cannot be reset during a measurement or while the instrument is in stand-by mode.