4.11
KEW6305
1 5 0 V 3 0 0 V 6 0 0 V
1 P 2 W 1 P 3 W 3 P 3 W 3 P 4 W
5 A
1 0 A
2 0 A
5 0 A
1 0 0 A 2 0 0 A 5 0 0 A 1 0 0 0 A
“
Setting 09” Recording interval
Following explains how to set the recording interval for integration/ demand measurement.
The recording interval is a time distance to record each measurement data into SD Card or internal
memory.
Setting time
1 / 2 / 5 / 10 / 15 / 20 / 30 sec.,
1 / 2 / 5 / 10 / 15 / 20 / 30 min.,
1 hour
Default value (or after system reset)
30 min.
1 Use the
Cursor
key on the selection screen, and select “Setting 09”.
2 Press the
ENTER
key to get the instrument into setting change mode.
3 Previous setting (or default value: 30 min.) blinks. Press the
Cursor
key to select any desired time,
and then press the
ENTER
key after making necessary change.
NOTE:
* Selectable interval is limited by the setting done at Setting 16 (Demand measurement cycle).
- An interval greater than the value set at Setting 16 cannot be selected.
- The interval should be divisible by the value set at Setting 16.
- Any of above interval is selectable if “NO” is selected at Setting 16.
Hour Minute
Second
www.
GlobalTestSupply
.com