Connection
Step 3: Insert the alarm terminal block into its socket.
Wiring and mounting should meet the following specifications
Table 8 Wiring and Mounting Specifications
Terminal Block type
Torque requirements
Cross-sectional area (AWG)
Plug-in Terminal Block
4.5-5.0 lb-in
12-24
4.8 DI/DO Interface
The input and output terminals are located on the lower right side of the front panel, which
provides two low drive input signal acquisition, high drive output ability, the input is
optocoupler isolated acquisition, and the output is normally-open and normally-close
output.
When device works normally, the delay output terminal block (DO/GND) is normally-open;
when valid signal is received by input end, the delay output close.
Input Voltage
Availability
Output status
0-1.0VDC
Invalid
Normally-open
1.2-30VDC
Valid
Output close
(1) Input electrical parameters:
Input Voltage
0-30VDC
(2) Output electrical parameters:
Rated load
AC125V 0.5A
;
DC30V 2A
Rated current
2A