Connection
4.7 Alarm Terminal Block
The alarm terminal block is located on the cover plate of the device for alarm output.
When the device works normally, the alarm relay normally-open contact is on, and normally-
close contact is off; When an alarm occurs, normally-open contact is off and normally-close
contact is on. The normally-open and normally-close contact of delay is output through the 3-
pin 5.08-spacing plug-in terminal blocks.
Figure 14 3-Pin 5.08mm-Spacing Plug-in Terminal Block (Socket)
Electrical parameters of relay:
Maximum voltage: 250VAC/220VDC
Maximum current: 2A
Maximum power: 60W
Maximum insulation withstand voltage: 2KV
Note:
Pin 1 and Pin 2 is a normally-open contact, Pin 2 and Pin 3 is a normally-close contact. When
the device works normally, it is close between Pin 1 and Pin 2, it is open between Pin 2 and
Pin 3; when an alarm occurs, it is open between Pin 1 and Pin 2, it is close between Pin 2 and
Pin 3.
Copper conductor must be used for field wiring and the temperature should meet
75
℃
.
Wiring and Mounting
Step 1: Remove the alarm terminal block from the switch.
Step 2: Fix the three wires for alarm into the alarm terminal block according to the above
note.