7 Flue gas measurement
7 Flue gas measurement
7
MEASURING FLUE GAS – GENERAL INFORMATION
7.1
Brief information on flue gas values
Designation Abbreviation
Good
value
Comment
Carbon dioxide
CO
2
10 - 11.5 %
Jointly responsible for the greenhouse effect. The CO
2
that
occurs with combustion is bonded as a plant nutrient by the
growing wood. Consequently wood is “CO
2
neutral”.
Oxygen O
2
8.5 - 10 %
Residual oxygen from the combustion air
Carbon monoxide
CO
<500 -
1000 mg/Nm³
13 % O
2
Strong blood toxin; prevents transport of oxygen in the blood,
is quickly decomposed in air.
Nitrogen oxide
NO
x
<200 -
500 mg/Nm³
13 % O
2
Respiratory toxin; highly dependent on the nitrogen content
of the fuel; the limit values must only be complied with for
nitrogen content < 0.15 % by weight.
Hydrocarbons
HC
A wide variety of harmful compounds, “wood fire odour”, they
behave like CO, complex measurement
Dust <50
mg/Nm³
13 % O
2
Fine fly ash and particles of soot, depending on the dust content
of the fuel
Firing efficiency
Eta [
η
]
>88 - 95 %
depends on CO
2
content and flue gas temperature, (approximate
boiler effi 2 %)
7.1.1
Emission value units
Unfortunately a standard unit is not used for emission values in the different directives and standards. To be
precise, the conversion is quite complex because many influence factors must be taken into consideration. The
accompanying table suffices for an approximate estimate calculation.
Abbreviation
Designation
Comment
% CO
2
and O
2
Percentage by volume (m³/m³)
Measured in dry flue gas (without water vapour)
ppm
parts per million (cm³/m³)
= 0.0001 percentage by volume
mg/Nm³ 10 % O
2
Milligrams per standard cubic
meterResidual oxygen in the flue
gas 10 %
Reference value is 1 cubic meter flue gas at 0 °C and 1.013 bar
and a residual oxygen content of the flue gas of 10 %
mg/MJ
Milligrams per mega joule
Reference value is the lower heating value of the fuel in MJ
mg/kWh
Milligrams per kilowatt hour
Reference value is the lower heating value of the fuel in kWh
MA-Easyfire 10.2008_EN.indd 71
MA-Easyfire 10.2008_EN.indd 71
30.03.2009 13:30:11 Uhr
30.03.2009 13:30:11 Uhr
Содержание Easyfire
Страница 1: ...Biomass Heating Systems Pellet boilers KWB Easyfire 10 30kW Installation and Maintenance Manual...
Страница 45: ......
Страница 59: ......
Страница 63: ......
Страница 69: ......
Страница 77: ......
Страница 95: ......
Страница 107: ......
Страница 113: ......
Страница 143: ......
Страница 161: ......
Страница 181: ......
Страница 213: ......
Страница 218: ...Notes...
Страница 219: ...Notes...