DSP-30

 

Percent Power Meter Display Module 

 
 
 
 
 
 
 
 
 
 
 

 

Front Panel Display 

DSP-30  Display  panel  has  three  four  Digits  bright  L

ED’s  that 

shows (RMS) Voltage, Amps and percentage of full Power. The 
user  can  easily  read  the  real  time  3  phase  Voltage,  Amps  and 
the percent of power that load is using now. 

Programming Mode 

There  are  three  push  buttons  on  the  front  panel  for  100%  full 
power  range  setting.  User  need  to  set  the  full  power  range  in 
KVA  before  used.  The  buttons  function  description  show  as 
below. 

 

Program key

Press it will into program mode. 

V

 

Up key

Press it will increase the setting value. 

A

 

Down key

Press it will decrease the setting value. 

How to Program the DSP-30 

(1KVA / Unit)

 

Step-1

Press  the  program  key  for  2  seconds  and  then  the 
DSP-30 will into program mode and the screen show as 
below. 

Step-2

Use Up or Down key for 100% power range setting. 

Step-3

Press program key again to exit the program mode. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Display Function 

The  operator  can  change  the  voltage  and  current  display  to  be 
fixed or cycling from phase to phase by simply using the button 
next to each display. 

To change the display mode, press the button next to it. See diagram. 

Rear Panel Layout

 

 
 
 
 
 
 
 
 
 
 
 
 
 

Recommended Cut-Out

66

66 ± 0.5 mm

 

Voltage and Current Adjustment (If Necessary) 

In the back of the DSP-30 module we have 4 push buttons for voltage 

V

 & V

  and current 

A

 & A

  adjustment. The Module comes 

factory tested and calibrated and normally no changes are necessary. 
But if any modifications are required, follow the procedures below. 

Voltage Adjustment 

(Please use and accurate RMS Voltmeter as your reference) 

1. Start the generator. Set your reference AC voltage using your 

Voltmeter. 

2. Select the desire phase you need to re-calibrate using the front 

display 

V

  button on the display and hold. 

3. Repeatedly press 

V

) or 

V

  on back of module to adjust 

the displayed voltage equivalent to your voltmeter. 

4. Release  the  front 

V

  button.  The  LED  display  will  flash 

continuously for 5 seconds. 

5. After  for  5  seconds  then  the  system  will  automatically  record 

the new setting and return to normal. 

6. If the display shows 

FAIL

  the setting is invalid, and step 3 

must be repeated. 

Current Adjustment Procedure 

(Please use Standard RMS Current meter for readings) 

1. Set the dip switches to the correct 

CT

  in use. 

2. Start the generator. And wait for the generator to stabilize. 
3. Slowly  add  load  to  the  genset  until  maximum  rated  load 

current is reached for the CT in use. 

4. Select desire phase current to calibrate using the front  A   button. 
5. Repeatedly press  A

  or  A

  on the back panel to adjusts 

the displayed current to its equivalent on the current meter. 

6. Release  the  front 

A

  button.  The  LED  on  the  display  will 

flash continuously for 5 seconds. 

7. After  5 seconds  the  system  will  automatically  record the  new 

setting and return to normal. 

8. If the panel display shows 

FAIL   then the previous setting is 

invalid, please return to step 5. 

 

 

 
 

 

 
 