4.2.3 Function
See page 24
4.2.3.1 Module status
State
LED
Explanation
U24_Load
BOOL
Undervoltage (Supply < 19,2V)
U24_Logic
BOOL
Undervoltage (Supply < 19,2V)
ShortcutOutput
BOOL
Short circuit on a digital output
4.2.4 Technical Data
Function ......................................................... Connects a 100 Base-TX EtherCAT with the Ventura FIO I/O
modules
Generates the LVDS system voltages (E-bus)
IO-module
Controller ....................................................... ASIC ET1100
Baud rate ....................................................... 100 Mbit/s
Cable ............................................................. CAT5
Length of cable .............................................. max. 100m between 2 bus couplers
Ports ............................................................. 2x RJ45
Power supply ................................................. 24 VDC -20% +25%
Connector Power ........................................... Plug 2-pole (part of the module)
Input current .................................................. 40mA & E-bus power supply
E-bus power supply ....................................... max. 2A (approx. 11 modules)
E-Bus Connector .......................................... 10-pole system plug in the side wall
End module ................................................... not necessary
Digital Inputs .................................................. 16
Input delay ..................................................... 3 ms (typically)
Signal level .................................................... Off:
-3 … 5V
(EN 61131-3, type1)
On:
15V … 30V
Digital Outputs ............................................... 16
max. current ................................................... 0.5A per output
Sum current ................................................... max. 8A
Part no. .......................................................... 694.400.10
Approvals .......................................................
(planned)