Kendrion Kuhnke Automation GmbH
Software
143
11/25/2016
6 Configuration
The EtherCAT master needs to be configured to drive the EtherCAT network.
One major part of the configuration is to specify the EtherCAT slave stations.
There are two ways of documenting the properties of an EtherCAT slave.
1. The basic properties are stored in an EEPROM of the slave, whereas a XML device file describes
the others.
2. All of the properties are stored in an EEPROM of the slave. (This method is not supported by every
OEM supplier.)
The XML device files provide EtherCAT administrators with convenient options.
EtherCAT allows both, a configuration offline and the scanning of station data via an Ethernet line (online
configuration).
The examples below are based around the standard ETG configuration tool (EtherCAT configuration tool
supplied by Beckhoff Automation GmbH) which accesses the XML device files for both offline and online
configuration.
The file to use for Ventura FIO is called
"KuhnkeEtherCATModulesAll.xml"
.
Copy the file "KuhnkeEtherCATModules.xml" to folder C:\Programs\EtherCAT Configurator\EtherCAT or, if
you are using another tool, to the folder set for that tool.
6.1 CoDeSys V2 (Beckhoff Configurator)
6.1.1 Offline Configuration
Run the EtherCAT configuration tool.
Choose File, New to create a new I/O Configuration.
Select "I/O Devices" and run "Append Devices". This will add "Device 1 (EtherCAT)" to your
configuration, i.e. a new EtherCAT line
Select "Device 1 (EtherCAT)" and run "Append Box".
Expand the branch labeled "Kuhnke" and its sub-branch and select "Bus coupler (694.400.00)".