4 Installation
Kübler Group
22 | EN
Operation Manual R60087.0009 - 03
Wiring
When wiring the facility, pay attention to proper cable routing.
• Separate the wiring into power groups such as motor/power
supply lines and signal and data lines.
• Route the signal and data lines as close as possible to
ground surfaces (frames, metal rails, cabinet sides) and not
parallel to motor and power supply lines or other lines carry-
ing high interference levels.
• Do not connect other users with high interference levels
(such as frequency converters, solenoid valves, contactors)
to the power supply of the device.
4.2 Electrical Installation
4.2.1 General Information for the Connection
ATTENTION
Destruction of the device
Before connecting or disconnecting the signal cable, always
disconnect the power supply and secure it against switching
on again.
NOTICE
General safety instructions
Make sure that the whole plant remains switched off during
the electrical installation.
Make sure that the operating voltage is switched on or off
simultaneously for the device and the downstream device.
NOTICE
Other operating instructions applicable for the installa-
tion
To connect the device, refer to the corresponding operating
and safety instructions of the external drive system / evalu-
ation system / control.
When assembling a mating connector, comply with the in-
structions attached to the connector.
NOTICE
No open cable wires
Connect all required cable wires / connectors before commis-
sioning. Insulate individually all unused ends of the output
signals to avoid short-circuits.
• Electrostatic discharges at the contacts of the connector or
at the cable ends could damage or destroy the device. Take
appropriate precautionary measures.