5 Installation at Site
38 of 98
UPA / UPA S
3400.86/17-EN
2
3
4
1
5
Sizes 2, 3, 3a, 3b, 4
Sizes 6 to 9
Size 11
1 = turnbuckle (reusable)
2 = cable guard
3 = power cable
4 = metal strap
5 = riser
1. Cut the metal strap (4) to size (length L = circumference of riser + approx.
200 mm allowance) and bend approximately 100 mm of both strap ends
inwards.
2. Fully open the turnbuckle (1) and attach it to one end of the metal strap (4).
3. Place the cable guard (2) around the power cable (3). Place it around the riser
(5) together with the metal strap (4). Then attach the other end of the
turnbuckle (1) to the metal strap (4).
4. Tighten the turnbuckle (1) with a screwdriver so that the power cable (3) cannot
slip downwards by its own weight!
5.4 Installing the pump set in a horizontal position
WARNING
Installation on a mounting surface which is unsecured and cannot support the load
Personal injury and damage to property!
▷
Use a concrete of compressive strength class C12/15 which meets the
requirements of exposure class XS1 to EN 206.
▷
The mounting surface must be set, even, and level.
▷
Observe the weights indicated.
CAUTION
Temperature and pressure increase of the motor fill
Damage to the motor!
▷
Always protect non-flooded pump sets against direct exposure to sun.
NOTE
Only install the pump set in a horizontal position if it has been explicitly approved
for this type of installation.
A submersible borehole pump can be installed in a horizontal position, provided the
pump set is designed for this type of installation. See order documentation.
The required accessories depend on the weight and the overall length of the pump
set.
▪
If agreed with KSB, the pump set is supplied with the accessories for the required
installation type already fitted.
▪
Using original accessories (pedestal, supporting frame, pressure shroud) is
imperative for assembly at the site.