The pumps can be operated in manual mode in two different ways.
▪
Each pump can individually be operated in manual mode by using the multi-
functional button of the control panel. Select the desired pump by pressing the
multi-functional button either once or twice and holding it down. The
corresponding pump will then be operated in manual mode as signalled by the
blinking green LED.
▪
A manual-0-automatic selector switch is provided for each pump at the control
cabinet, which makes it possible to operate each pump in manual mode. The
"manual" position is momentary, i.e. the manual-0-automatic selector switch
snaps back to the "0" position when released.
NOTE
Continuous manual mode is reserved exclusively for emergencies!
Continuous operation of the pressure booster system in manual mode may result in
waste of energy and water.
Continuous operation of the pressure booster system in manual mode may cause
the fluid handled and the pump to overheat.
In manual mode, a minimum flow (as shown in table below) is essential to prevent
the fluid handled and the pump from overheating when no water is consumed at the
consumer installations.
Pump
Minimum flow per pump in manual
mode
[l/h]
Etabloc 32
15 % of Q
opt
Etabloc 40
15 % of Q
opt
An open
1
/
2
-inch tap equals a water consumption of approx. 800 to 1,200 l/h.
4.6 Noise characteristics
For the noise level of the individual pumps please refer to the pump's operating
instructions.
4.7 Scope of supply
Depending on the model, the following items are included in the scope of supply:
System
▪
Two horizontal single-stage Etabloc volute casing pumps
▪
Membrane-type accumulator on the discharge side
▪
Pressure transmitter on the discharge side
▪
Pressure gauge
▪
Powder-coated steel baseplate
Per pump:
▪
Check valve
1)
▪
Shut-off valves
Control cabinet
▪
Multi-functional button (for manual operation, setting the start-up pressure,
fault acknowledgement)
▪
Three LEDs signalling the operating status
▪
Motor protection switch per pump
▪
Protective switch for mains and transformer
▪
1 manual-0-automatic selector switch per pump ("manual" position momentary)
Function
Manual mode
Example
1)
Connection types C and V only
4 Description
14 of 40
Surpress Feu SFE.3
Содержание Surpress Feu SFE.3
Страница 1: ...Fire fighting System Surpress Feu SFE 3 From series 2014w33 Installation Operating Manual...