The Other Setpoint process type can be used to set other control modes such as level
control and differential temperature-dependent control.
Controller optimisation
Attenuation and response speed of the closed control loop can be optimised using
the PI Prop Gain
(3-9-1-2)
and PI Integral Tm
(3-9-1-3)
parameters.
When beginning to optimise the controller, the values for PI Prop Gain
(3-9-1-2)
and
PI Integral Tm
(3-9-1-3)
should only be adjusted in small increments.
Depending on its value, the proportional gain of the controller PI Prop Gain
(3-9-1-2)
has the following effect on the control characteristics:
▪
Low value selected for PI P Prop Gain
(3-9-1-2)
: Moderate controller response
speed and small overshoot
▪
Large value selected for PI P Prop Gain
(3-9-1-2)
: Faster controller response and
larger overshoot
7 Commissioning/shutdown
58 of 162
PumpDrive