All alerts are acknowledged at the same time during a reset. Resetting is initiated via
the control panel by pressing the OK key and is only possible in the start menu. You
may therefore need to press the ESC key several times to return to the start menu.
The reset can also be carried out via a digital input. Digital input 4 is defaulted for
Automatic reset
Alerts can also be reset automatically (3-11-2-1). This parameter is defaulted to
automatic reset (
Overview of warnings and alerts (
6.2.5.3
Menu: Settings
General settings can be made or the settings for the process optimised in the Settings
section. All aspects that have to do with the operative function or availability of the
pump set can also be found here.
6.2.5.3.1 Setting the display language
The following display languages can be toggled:
▪
German
▪
French
▪
English
▪
Italian
Table 41: Language parameters
Parameter
Description
Possible
settings
Access
Factory setting
3-1-1-1
Display
language
German
French
English
Italian
Customer
English
6.2.5.3.2 Access levels
Four access levels have been defined to prevent accidental or unauthorised access to
PumpDrive parameters:
Table 42: Access levels
Access level
Description
Standard (No Login)
Access without password entry.
Customer
Access level for the expert user with
access to all parameters required for
commissioning.
Service
Access level for service personnel.
If a parameter's access level is not explicitly specified, the parameter is always
assigned the customer access level.
Table 43: Access level parameters
Parameter
Description
Possible settings
Access level required
Factory
setting
3-1-6-1
Enter customer password for
access
0000...9999
Standard
0000
3-1-6-2
Enter service password for access 0000...9999
Service
-
3-1-6-4
Change customer access level
password
0000...9999
Customer
-
3-1-6-5
Password-protected access level
for customer parameter
Disabled
Enabled
Customer
Disabled
Reset
6 Operation
46 of 162