Message
Description
PumpDrive
response
Network error
Network error
Service required
Motor I2t
Impermissible overcurrent
Speed reduction
IGBT Temperatur
Power electronics overtemperature
Stop
Case Temperatur
Impermissible heat sink temperature
Stop
High Timeout
Impermissible hydraulic overload
Q Low Timeout
Impermissible hydraulic part load (low flow)
CAN ID Not Allo
KSB local bus ID query could not be processed Service required
Q estimation
The pump is operated outside the limits of the
set H/Q data points or P/Q data points, or the
data points have been entered incorrectly.
Warning only
Table 113: Warnings
Warning
Possible causes
Remedy
Current Limit/
Motor I2t
Incorrect motor data set (
3-3-2
)
Match motor data settings to motor used.
Wrong direction of rotation of the pump
Change the direction of rotation of the motor via
the phase sequence.
Hydraulic overload
Reduce the hydraulic load.
Pump blocked mechanically/runs sluggishly
Check pump.
Motor terminal board wired incorrectly
(delta/star)
Wire motor terminal board correctly.
PumpDrive rating < motor rating or
Output current < motor current
Wrong device ordered; mount larger PumpDrive
model.
Frequency inverter carrier frequency
(3-11-1-1)
set too high
Set carrier frequency to permissible range
(
Ambient temperature of PumpDrive > 40 °C Impermissible operating range; mind power
- Fluctuating DC link voltage
(1-4-1-1)
when
pump is not running
Check mains voltage quality.
Fluctuating DC link voltage
(1-4-1-1)
when
pump operates at rated values
Check mains voltage quality.
Incorrect motor current measurement
(1-2-1-5)
Measure current using suitable snap-on ammeter
and compare with
(1-2-1-5)
.
NOTE! Approx. 10 % tolerance is permissible.
Pump runs in reverse when motor is not
supplied with current
Check swing check valve.
PumpDrive output current set too low
Slightly increase
(3-6-1-4)
to enable higher
PumpDrive output current.
Motor voltage output is too low at rated
load,
(1-2-1-3)
< 380 V at rated load
Check line input voltage; enter motor current at
380 V mains voltage; fit larger-sized motor.
Motor voltage too low
Change V/f characteristic to Linear (
7.2.6.2 Page 93) ; take nominal motor voltage
into account; check mains voltage.
Network error
KSB local bus wired incorrectly (interruption,
short circuit)
Re-wire properly.
Sensor connected incorrectly
Connect sensor properly; check whether
(3-9-1-1)
has been enabled.
No main pump recognised in system
Set (
3-2-1-1
) to AuxMainpump on main pump
with sensor.
Ctrl Timeout
PI mode
(3-9-1-1)
; sensor has not been
recognised
Connect sensor properly; check whether
(3-9-1-1)
has been enabled.
Live zero monitoring in a multiple pump
system has been triggered
Replace defective sensor with new one.
Advanced HMI in a multiple pump system
has failed
Replace defective Advanced HMI with new one.
IGBT Temperatur
Ambient temperature of PumpDrive > 40 °C Impermissible operating range; mind power
Internal/external fans do not work
(1-4-1-3)
> 50 °C
→
External fans must run.
Heat sink/cooling fins dirty
Clean heat sink/cooling fins.
11 Trouble-shooting