5 Installation/Commissioning
15 of 40
KSB Guard
5 Installation/Commissioning
5.1 Installation
5.1.1 Installing the gateway
DANGER
Risk of falling when working at a great height
Danger to life by falling from a great height!
▷
Do not step onto the pump (set) during installation work or dismantling work.
▷
Pay attention to safety equipment, such as railings, covers, barriers, etc.
▷
Observe the applicable local health and occupational safety regulations and
accident prevention regulations.
WARNING
Work in the immediate vicinity of rotating parts
Risk of hand injury!
▷
Always have this work performed by trained personnel.
▷
Take particular caution when performing this work.
CAUTION
Incorrect installation
No data transmission!
▷
Never connect more than 20 transmission and battery units to a gateway.
▷
Maintain a minimum distance of approx. 100 m between 2 gateways (or use
separate rooms/ halls).
One gateway can process the data of up to 20 transmission and battery units if they
send data every hour. This number is reduced with more frequent data transmission.
The manufacturer must be consulted if more than 20 transmission and battery units
are connected or if the data transmission rate is higher.
NOTE
Adding another gateway will not serve to increase the data transmission rate or the
number of connected transmission and battery units. If several gateways are within
transmission range of each other, this can lead to overlap and interference.
5.1.1.1 Checking the installation location of the gateway
The installation location of the gateway must meet the following requirements:
▪
Temperature 0 - 40 °C
3)
▪
Only install and operate the gateway in closed rooms.
▪
No direct sunlight
▪
At least 2 m above the ground
▪
Maximum distance between gateway and transmission and battery unit: 30 m
▪
Area between gateway and transmission and battery unit with as few obstacles
as possible (e.g. walls).
If possible: Install with a direct visual connection between the pump set to be
connected and the gateway.
3)
Higher temperatures than indicated are possible. Contact KSB Support for more information.
Содержание Guard
Страница 1: ...KSB Guard Installation Operating Manual ...
Страница 4: ...Contents 4 of 40 KSB Guard 11 EU Declaration of Conformity 35 Index 36 ...
Страница 26: ...6 Operation 26 of 40 KSB Guard The device then automatically switches to stand by mode and all LEDs extinguish ...
Страница 38: ......
Страница 39: ......
Страница 40: ...KSB SE Co KGaA Johann Klein Straße 9 67227 Frankenthal Germany Tel 49 6233 86 0 www ksb com 4079 8 01 EN ...