4 Description of the Pump (Set)
14 of 62
Etanorm FXV
1311.83/06-EN
4 Description of the Pump (Set)
4.1 General description
▪
Volute casing pump for sprinkler installations to VdS CEA 4001
4.2 Product information as per Regulation No. 1907/2006 (REACH)
For information as per chemicals Regulation (EC) No. 1907/2006 (REACH), see
www.ksb.com/ksb-en/About-KSB/Corporate-responsibility/reach/
4.3 Designation
Example: Etanorm FXV 065-040-250 GB 10
Table 4:
Designation key
Code
Description
Etanorm
Type series
FXV
Additional code
F
Fire-fighting pump
X
Special design
V
VdS-approved
065
Nominal suction nozzle diameter [mm]
040
Nominal discharge nozzle diameter [mm]
250
Nominal impeller diameter [mm]
G
Casing material
G
Cast iron
B
Bronze
S
Nodular cast iron
B
Impeller material
B
Bronze
C
Stainless steel
10
Shaft seal, e.g. Q1 Q1 X4GG
4.4 Name plate
KSB SE & Co. KGaA
Johann-Klein-Straße 9
67227 Frankenthal
Mat. No. 01493872
ZN 3814 - 36 DE
KSB Code
Jahr
VdS-Anerk.-Nr.
Q zul.
P
N
Fabr.-Nr.
mm
Umschaltstrom Y
→
Δ
1/min
n
N
Laufraddurchmesser
max. I
A
Direkt
l/min
A
A
Sprinklerpumpe Typ
H
m
P
M
kW
bar
ETNF 100-080-250 GBVA 10GB309002B
ETANORM FXV 100-080-250
2018
9971581385 000100 01
3.164,00
2940
269
94,70
90,00
12,00
P 4940416
1
2
3
4
5
6
7
8
9
10
11
12
13
Fig. 5:
Name plate (example)
1
KSB Code
2
Type series, size
3
KSB order number,KSB order item
number and consecutive number
4
VdS-approved flow rate
Содержание Etanorm FXV