6 Commissioning/Start-up/Shutdown
19 of 32
COBRA-TDC01/03
8194.8/02-EN
6.2.1 Pressure/temperature ratings
Table 5:
Permissible operating pressure [bar]
PN
Material
[°C]
-10 to 120
150
200
250
300
350
10
EN-GJS-400-15
10
9,7
9,2
8,7
8
7
16
16
15,5
14,7
13,9
12,8
11,2
25
25
24,3
23
21,8
20
17,5
40
40
38,8
36,8
34,8
32
28
6.2.2 Flow velocity
Table 6:
Permissible flow velocity with the valve fully open
[m/s]
10
3,0
16
4,0
25
5,0
40
6,0