3 Description
9 of 16
BACnet MS/TP Gateway
CAUTION
Operation without back-up battery
System malfunction!
▷
Never operate the device without a back-up battery.
3.3.4 Error code
In the event of a malfunction, the red LED indicates the respective operating
condition. If no malfunctions are present, the red LED illuminates continuously.
Otherwise, there are 3 fault statuses that are displayed with the following flash
codes:
Approx. 1 - 3 sec.
No communication with BACnet
Modbus fault (exception, timeout, broken line)
Gateway without valid configuration
When Modbus communication between the gateway and pump is interrupted, the
gateway automatically attempts to re-establish the connection every 3 minutes.
3.3.5 Technical data
Characteristic
Value
Power supply
9 - 30 V DC, approx. 20 mA at 24 V DC
Enclosure
IP20
Housing design
DIN rail assembly
Weight
Approx. 0.1 [kg]
Dimensions
W x H x D: 18 x 90 x 115 [mm]
Table 5:
Object list
Type-Instance
Object name
Value
Read/Write
Description
[V]
R
Replace battery on falling below
2.0 V
[m]
R
Head
[m³/h]
R
Flow rate
[rpm]
R
Speed
[h]
R
Operating hours
[W]
R
Power
[%]
R
Load between 0-100 %
[%]
R/W
Setpoint between 0-100 %
Normal / Fault
R
Temperature limit
Normal / Fault
R
Overcurrent
Normal / Fault
R
Internal fault
Normal / Fault
R
Rotor locked
Normal / Fault
R
Overload / adjusted speed
Normal / Fault
R
Supply voltage too high/low
Normal / Fault
R
Motor fault
Operate / Stop
R
Status
Start / Stop
R/W
Switch Start/Stop