5 Installation at Site
23 of 84
Amarex N
2563.84/08-EN
Fig. 3:
Checking the direction of rotation
3. If the impeller is running in the wrong direction of rotation, check the electrical
connection of the pump and the control system, if necessary.
4. Disconnect the pump set from the power supply and make sure it cannot be
switched on unintentionally.
5.3 Installing the pump set
Always observe the general arrangement drawing/outline drawing when installing
the pump set.
5.3.1 Stationary wet installation
5.3.1.1 Fastening the duckfoot bend
Fastening the duckfoot bend with chemical anchors
Depending on the pump size, the duckfoot bend is fastened with chemical anchors.
72-1
90-3.38
Fig. 4:
Fastening the duckfoot bend
1. Position duckfoot bend 72-1 on the floor of the tank/sump.
2. Insert chemical anchors 90-3.38.
3. Bolt duckfoot bend 72-1 to the floor with chemical anchors 90-3.38.
Chemical anchor
dimensions
t
2
t
1
SW
1
d
1
SW
2
d
2
l
1
Fig. 5:
Dimensions