7 Maintenance and fault rectification
OPTISOUND 3030 C • Foundation Fieldbus
51118-EN-210701
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
Error
Cause
Rectification
E013
no measured value available Sensor in boot phase
Sensor does not find an echo, e.g. due to faulty installation
or wrong parameter adjustment
E017
Adjustment span too small
Carry out a fresh adjustment and increase the distance be-
tween min. and max. adjustment
E036
no operable sensor software Carry out a software update or send instrument for repair
E041
Hardware error, electronics
defective
Exchange the instrument or send it in for repair
E113
Communication conflict
Exchange the instrument or send it in for repair
Depending on the reason for the fault and the measures taken, the
steps described in chapter "
Setup
" must be carried out again or must
be checked for plausibility and completeness.
7.3 Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
In Ex applications, only instruments and electronics modules with ap-
propriate Ex approval may be used.
If there is no electronics module available on site, one can be ordered
from the Krohne agency serving you.
7.4 How to proceed if a repair is necessary
If it is necessary to repair the instrument, please contact the responsi-
ble Krohne agency.
Error messages via the
display and adjustment
module
Reaction after fault recti-
fication
Содержание OPTISOUND 3030 C
Страница 1: ...OPTISOUND 3030 C Handbook Ultrasonic Level Transmitter Foundation Fieldbus ...
Страница 3: ...3 Contents OPTISOUND 3030 C Foundation Fieldbus 51118 EN 210701 Editing status 2019 03 12 ...
Страница 50: ...50 Notes OPTISOUND 3030 C Foundation Fieldbus 51118 EN 210701 ...
Страница 51: ...51 Notes OPTISOUND 3030 C Foundation Fieldbus 51118 EN 210701 ...