25
6 Set up with the display and adjustment module
OPTISOUND 3030 C • Foundation Fieldbus
51118-EN-210701
6.3 Setup steps
The sensor measures the distance from the sensor to the medium
surface. For indication of the real level, an allocation of the measured
distance to the percentage height must be carried out.
The actual level is then calculated on the basis of these entered
values. At the same time, the operating range of the sensor is limited
from maximum range to the requested range.
100%
0%
0,25
m
(9.8
4")
5
m
(196.
9")
2
1
3
Fig. 25: Parameterisation example, Min./max. adjustment
1 Min. level = max. distance (depending on the sensor)
2 Max. level = min. distance (final value of the dead zone, depending on the
sensor)
3 Reference plane
The actual product level during this adjustment is not important,
because the min./max. adjustment is always carried out without
changing the product level. These settings can be made ahead of
time without the instrument having to be installed.
Proceed as follows:
1. Move from the measured value display to the main menu by
pushing
[OK]
.
▶
Basic adjustment
Display
Diagnostics
Service
Info
2. Select the menu item "
Basic adjustment
" with
[->]
and confirm
with
[OK]
. Now the menu item "
Min. adjustment
" is displayed.
Min. adjustment
0.00 %
=
5.000 m(d)
4.000 m(d)
Parameter adjustment
Basic adjustment - Min.
adjustment
Содержание OPTISOUND 3030 C
Страница 1: ...OPTISOUND 3030 C Handbook Ultrasonic Level Transmitter Foundation Fieldbus ...
Страница 3: ...3 Contents OPTISOUND 3030 C Foundation Fieldbus 51118 EN 210701 Editing status 2019 03 12 ...
Страница 50: ...50 Notes OPTISOUND 3030 C Foundation Fieldbus 51118 EN 210701 ...
Страница 51: ...51 Notes OPTISOUND 3030 C Foundation Fieldbus 51118 EN 210701 ...