background image

GB-11

D

GB

F

NL

I

E

 0 

 When the furnace chamber has cooled down, 

check the burner tube and burner quarl through 
the furnace flange.

22

23

24

21 

New gas 
housing 
gasket.

 

Tighten the burner insert with max. 37  Nm 

(27.3 lb ft).

 5 

  Connect the system to the electrical power sup-

ply.

 

6 

 Open the gas and air supply.

27

 8 

  Set the burner to low fire and compare the pres-

sure settings to those stated in the acceptance 
report.

 9 

  Set the burner to low and high fire several times 

while monitoring the pressure settings, flue gas 
values and flame patterns.

 DANGER

Risk of explosion and poisoning during burner 
adjustment with an air deficiency!

 Adjust the 

gas and air supply so that the burner is always oper-
ated with excess air – otherwise CO will form in the 
furnace chamber. CO is odourless and poisonous! 
Conduct a flue gas analysis.

 0 

 Produce a maintenance report.

Assistance in the event of 
malfunction

 DANGER

Electric shocks can be fatal! Before working on 
possible live components, ensure the unit is discon-
nected from the power supply.
Risk of injury! Burner heads have sharp edges.
Fault-clearance must only be undertaken by author-
ized trained personnel.

 

If no fault is detected when checking the burner, 
proceed to the automatic burner control unit and 
check for faults in accordance with the relevant 
operating instructions.

 ? 

 

Faults

 ! 

 

Cause

  • 

 

Remedy

 ? 

  

Burner does not function?

 ! 

   Valves do not open.

  • 

 Check the voltage supply and wiring.

 !  

Tightness control signals a fault.

  • 

 Check the valves for tightness.

  • 

 Note the tightness control operating instructions.

 !  

Control valves do not move to low-fire position.

  • 

 Check the impulse lines.

 !  

Gas inlet pressure is too low.

  • 

 Check the filter for dirt.

 !  

Gas and air pressures on the burner are too low.

  • 

 Check the restrictors.

 !  

Automatic burner control unit signals a fault.

  • 

 Check the ionization cables and ionization cur-

rent.

  • 

 Check whether the burner is adequately ground-

ed.

  • 

 Note the automatic burner control unit operating 

instructions.

Содержание ZIO 165

Страница 1: ...Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 11 11 The following chapters have been changed Checking the usage Installation Preparing commissioning Technical data Logistics Declaration of Incorporation Operating instructions D GB GB 1 Translation from the German 032...

Страница 2: ...ternal insulation 165 200 Burner size R H K Normal flame Long soft flame Flat flame B D G M Natural gas Coke oven gas town gas Propane propane butane butane Propane propane butane butane L Ignition lance 50 100 150 200 Burner tube length mm 35 135 235 Position of burner head mm 1 to 199 1E to 199E Burner head identifier High temperature version A to Z Construction stage Z Special version Part desi...

Страница 3: ...rning in an open combustion chamber Control High Low High Low Off continuous Type of burner head H Max capacity approx 80 depending on the outlet diameter of the burner quarl Medium to high flow velocity Flat flame burner quarl For industrial furnaces and kilns and for burning in an open combustion chamber Control High Low High Low Off continuous limited control range Type of burner head K Capacit...

Страница 4: ... units to prevent mechanical stress or transmission of vibration Ensure that the seals are undamaged DANGER Risk of explosion Ensure the connection is gas tight For connecting to ANSI NPT connections An adapter set is required for connection to ANSI NPT see page 12 Accessories Type Gas connection GA Air connection LA ZIO 165 1 11 5 NPT 4 57 ZIO 200 2 11 5 NPT 6 72 Flange hole diameter Weld flange ...

Страница 5: ...ion cable see automatic burner control unit operating instructions Connect the ionization electrode to the automatic burner control unit via the ionization cable Ignition electrode Z Length of ignition cable max 5 m 15 ft recom mended 1 m 40 For permanent ignition max ignition cable length 1 m 40 Lay the ignition cable individually and not in a metal conduit Install the ignition cable separately f...

Страница 6: ...st volume into the furnace chamber Determining the flow rates QGas PB Hu QLuft QGas λ Lmin QGas Gas flow rate in m3 h ft3 h PB Burner capacity in kW BTU h Hu Gas calorific value in kWh m3 BTU ft3 QLuft Air flow rate in m3 n h scfh λ Lambda air index Lmin Minimum air requirement in m3 n m3 n scf scf Use the lower calorific value Hu Information on the gas quality supplied can be obtained from the co...

Страница 7: ...xternaldia 9mm 0 35 patm pair 0 3 5 2 4 L Loosen the screw 2 turns Fully open the air supply patm pair 0 5 Low fire The burner must only be ignited at low fire be tween 10 and 30 of the rated capacity Qmax see type label Reduce the air supply on the air control valve and set the desired low fire rate e g using a limit switch or mechanical stop On air control valves with bypass the bypass orifice s...

Страница 8: ...n adjustable gas restrictor be installed upstream of the burner open the restrictor by approx a quarter Open the gas supply Ignite the burner The safety time of the automatic burner control unit starts to elapse If no flame forms check and adjust the gas and air pressures of the start gas adjustment In the case of operation with bypass e g when using an air gas ratio control check the bypass nozzl...

Страница 9: ... Cooling air While the burner is switched off and depending on the furnace temperature there must be a cer tain air flow for cooling the burner components 700 800 900 1000 1100 1200 1300 1400 0 6 4 2 5 3 1 0 12 8 4 10 6 2 ZIO ZIO KB E ZIO K Furnace temperature C Cooling air at 20 C air volume at rated capacity Cooling air at 450 C air volume at rated capacity Diagram the relative air volume in per...

Страница 10: ...ark plug 1 using the dowel pin 2 10 Adjust spark plug and electrode to the measured total length L 11 12 Turning the spark plug makes it easier to feed the electrode into the burner insert Checking the burner 16 13 14 15 If the burner insert is dismantled the gas housing gasket will have to be renewed 17 Place the burner insert in a safe place Depending on the amount of dirt or wear replace the ig...

Страница 11: ...t of malfunction DANGER Electric shocks can be fatal Before working on possible live components ensure the unit is discon nected from the power supply Risk of injury Burner heads have sharp edges Fault clearance must only be undertaken by author ized trained personnel If no fault is detected when checking the burner proceed to the automatic burner control unit and check for faults in accordance wi...

Страница 12: ...d setting Order number 05012009 Adapter set 8 8 For connecting ZIO to NPT ANSI connections Burner Adapter set Order No ZIO 165 BR 165 NPT 74922636 ZIO 200 BR 200 NPT 74922637 Nozzle set Available on request for connecting integrated ignition lances to NPT threads Technical data Gas supply pressure approx 20 to 50 mbar air supply pressure approx 25 to 40 mbar each depending on flame shape gas type ...

Страница 13: ...as Description Burner for gas Typenbezeichnung Type BIO BIOA ZIO BIC BICA ZIC BIOW ZIOW BICW ZICW Anhang I Artikel Annex I Article 1 1 3 1 1 5 1 3 2 1 3 4 1 5 2 1 7 4 Folgende harmonisierte Normen wurden angewandt The following harmonized standards have been applied Lotte Büren Sandra Runde Datum Date Konstrukteurin Designer Sandra Runde ist bevollmächtigt die speziellen technischen Unterlagen gem...

Страница 14: ...ns please contact your local branch office agent The addresses are available on the Internet or from Elster GmbH We reserve the right to make technical modifications in the interests of progress info kromschroeder com www kromschroeder com Contact Certification Approval for Russia Certified by Gosstandart under Technical Regulations Approved by Rostekhnadzor RTN ...

Отзывы: