Checking the usage
Intended use
Gas solenoid valve for safeguarding gas or air on
various appliances.
This function is only guaranteed when used within the
specified limits – see page 7 (Technical data). Any
other use is considered as non-compliant.
WARNING
Cleaning work on the solenoid actuator may not
be performed using high pressure and/or chemi-
cal cleaning agents. This can cause moisture to
get into the solenoid actuator and may lead to a
dangerous failure.
Type code
Code
Description
VG
Gas solenoid valve
0/5 – 65
Nominal size
R
F
Rp internal thread
Flange to ISO 7005
0
0
0
8
p
u max.
200 mbar
p
u max.
360 mbar
p
u max.
1 bar
p
u max.
1.8 bar
L
N
Slow opening, quick closing
Quick opening, quick closing
T
Q
K
Mains voltage: 220/240 V AC, 50/60 Hz
Mains voltage: 120 V AC, 50/60 Hz
Mains voltage: 24 V DC
Terminal connection box, IP 54
Screw plug at the inlet
Screw plug at the inlet and outlet
D
With flow adjustment
M
Suitable for biologically produced
methane
V
Viton valve disc seal
Z
With rolling diaphragm
Part designations
6
5
1
3
4
2
1
3
2
5
7
Housing
Solenoid actuator
Connection box
4
Damping unit
5
Screw plug for inlet pressure p
u
6
Screw plug for outlet pressure p
d
7
VG 10/15 – 40/32: hexagonal nut (actuator)
VG 40 – 65: cap
Type label
Rated voltage, electrical power consumption, instal-
lation position, max. inlet pressure p
u max.
, ambient
temperature, enclosure and medium: see type label.
www.kromschroeder.com
Osnabrück, Germany
VG
CE - 0063CM1188
Installation
CAUTION
Please observe the following to ensure that the VG
is not damaged during installation and operation:
– Do not clamp the unit in a vice. Only secure the
flange by holding the octagon with a suitable
spanner. Risk of external leakage
.
– Do not install or store the unit in the open air.
– Check max. ambient temperature – see type
label.
– Check max. inlet pressure – see type label.
▷
Installation position: black solenoid actuator in
the vertical upright position or tilted up to the
horizontal, not upside down.
> 20 mm
▷
The housing must not be in contact with masonry.
Minimum clearance 20 mm (0.79").
> 20 mm
▷
Sealing material and dirt, e.g. thread cuttings,
must not be allowed to get into the valve housing.
▷
Install a filter upstream of every system.
▷
Use approved sealing material only.
▷
Use a suitable spanner.
▷
Ensure that there is sufficient space for installa-
tion and adjustment.
▷
On VG 10/15 – 40/32, the inlet pressure p
u
can
be measured at the pressure test point
p
u