UVS 10 with UVS 1 adapter
2
1
Cable selection
▷
▷
Use mains cable suitable for the type of operation
and complying with local regulations.
▷
▷
Signal line ≤ 2.5 mm².
▷
▷
The cable gland on the UVS 10..G1 or on the
socket of the UVS 10..P2 is suitable for cable
diameters of 7 to 13 mm.
Cable installation
▷
▷
Avoid external electrical interference.
▷
▷
Lay cables individually and, if possible, not in a
metal conduit.
▷
▷
Do not lay UV cable and ignition cable together
but lay them as far apart as possible.
Wiring
WARNING
Electric shocks can be fatal! Before working on
possible live components ensure the unit is discon-
nected from the power supply.
1
Disconnect the system from the electrical power
supply.
2
Shut off the gas supply.
UVS 10..G1
Route the cables through the M20 cable gland.
4
Wire the UV sensor as shown in the wiring dia-
gram for the correctly selected automatic burner
control unit, flame detector or burner control unit,
including the PE wire.
1 2 3
UVS 10..P2
2
1
3
4
3
6
7
5
Wire the socket as shown in the wiring diagram
for the correctly selected automatic burner control
unit, flame detector or burner control unit, including
the PE wire.