Checking the usage

UVS 10

UV sensor for flame control of gas burners, only in 
conjunction with Elster Kromschröder automatic 
burner control units IFS, IFD, PFS and PFD, flame 
detectors IFW or PFF or burner control units BCU 
or PFU.

This function is only guaranteed when used within 

the specified limits – see also “Technical data”. Any 
other use is considered as non-compliant.

Type code

Code

Description

UVS

UV sensor

10

Series 10

D
L

Quartz glass heat guard

Quartz glass heat guard lens

0

2
 

4

Rp 1/2 internal thread

Rp 1/2 internal thread and cooling air 

connection

1/2 NPT internal thread

1/2 NPT internal thread and cooling air 

connection

UVS 1 Adapter (28 mm (1.1”))

G1
P2

Electrical connection

M20 cable gland

4-pin plug, with socket

Part designations

1

2

4

3

6

5

7

8

UVS 10..G1

UVS 10..P2

1

  Housing

2

  Cable gland

  UV tube

4

  Adapter with quartz glass

5

  Plug

6

  Socket

7

  Retaining screw

8

  Seal

Installation

 CAUTION

Please observe the following to ensure that the 
UVS is not damaged during installation:

–   Use UV sensor only in conjunction with Elster 

Kromschröder automatic burner control units, 
flame detectors or burner control units.

–   Cool UV sensor with filtered air when subject 

to higher temperatures (see “Accessories”). In 
addition, this protects the sensor from dirt and 
condensation.

< 400 mm

(16”)

Cooling air

Max. distance between UVS and flame < 400 mm 
(16”).

It can be fitted using a ½” viewing tube that should 
be aligned on the first flame third, as this is where 
the highest UV radiation is generally found. The 
inside of the steel tube should not be coated 
and the tube should be directed at the flame 
from above so that no dirt collects in front of 
the UV sensor.

The UVS..L with quartz glass lens must be pre-

cisely aligned with the flame.

The UV sensor may only be exposed to the UV 

light of its own flame. It should be protected from 
other sources of ultraviolet light, e.g. neighbouring 

flames (this must be observed when monitor-

ing pilot and main burners in particular), ignition 
sparks, arcs from welding devices or lamps emit-
ting ultraviolet light.

Do not expose the UV sensor viewing opening 
to direct sunlight.

Supply cooling air to cool and protect the optical 
system from soiling and condensation.

Max. cable length in accordance with the speci-
fications for automatic burner control units IFS, 
PFS, PFD, flame detectors IFW, PFF or burner 
control units BCU, PFU.

UVS 10 with internal thread adapter

2

3

1

Содержание UVS 10

Страница 1: ...alified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Transport On receipt of the product check that the delivery is complete see Part designations Report any trans port damage immediately Storage Store the product in a dry place Ambient tempera ture see Technical data ...

Страница 2: ...ts flame detectors or burner control units Cool UV sensor with filtered air when subject to higher temperatures see Accessories In addition this protects the sensor from dirt and condensation 400 mm 16 Cooling air Max distance between UVS and flame 400 mm 16 It can be fitted using a viewing tube that should be aligned on the first flame third as this is where the highest UV radiation is generally ...

Страница 3: ... apart as possible Wiring WARNING Electric shocks can be fatal Before working on possible live components ensure the unit is discon nected from the power supply 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply UVS 10 G1 3 Route the cables through the M20 cable gland 4 Wire the UV sensor as shown in the wiring dia gram for the correctly selected automatic burner co...

Страница 4: ...Remote resets may only be conducted by au thorised personnel with continuous monitoring of the burner to be repaired Safe operation only in conjunction with Elster Kromschröder automatic burner control units flame detectors or burner control units Measure the current in the flame signal cable con nect the positive pole of the measuring instrument to the cable from the automatic burner control unit...

Страница 5: ...r Connect the UV sensor in accordance with the wiring instructions The automatic burner control unit performs a fault lock out during start up or operation The highly fluctuating flame signal temporarily exceeds the switch off threshold Reduce the distance between UV sensor and flame Position the UV sensor so that it can view the flame without hindrance e g smoke curtain Replace quartz glass disc ...

Страница 6: ...mschroeder com Contact Technical data Aluminium housing with integrated heat guard with connection terminals Clamping range of the connection terminals 2 5 mm Cable gland for cable diameters of 7 to 13 mm Distance between UV sensor and flame 300 400 mm UV tube P578 spectral range 190 270 nm max sensitivity 210 nm 10 nm Service life of the UV tube approx 10 000 operating hours Min DC signal 1 μA En...

Отзывы: