Labelling the PFA

 

Each PFA can be labelled individually.

  

 Attach label or sticker to the space provided on the 

handle of the fieldbus interface.

PFA

Zone 3

 

The size of this space is 28 × 18 mm 

(1.10 × 0.71").

Commissioning

 

During operation, the 7-segment display shows the 
program status:

 

 

––

   Unit Off

 

 

  Programming mode

 

 0.0.

  (blinking dots) Manual mode

 

 OP

  Normal operation

 

 P

  Profibus fault

 WARNING

Check the system for tightness before commissioning.
Do not start the PFA until the downstream automatic 
burner control units have been properly commissioned.

  

  Switch on the system.

 

The display indicates 

 ––

.

  

  Switch on the PFA by pressing the On/Off button.

 

As soon as the flashing display 

 P

 goes out and 

the display indicates 

 OP

, the data traffic is operating.

Manual operation

The PFA can be started in manual mode for burner adjust-

ment or for fault-finding:

 

Using the opto-adapter and the BCSoft software, the 
operating mode parameters for manual mode can 
be changed.

 CAUTION

If parameters are changed, stick the supplied adhesive 
label “Changed parameters” on the PFA – see page 12 
(Accessories).

  

  Switch on the system.

  

  Apply voltage to terminals 19 and 20 on the terminal 

strip X10.

  

  Switch on the PFA by pressing the On/Off button while 

holding down the Reset/Information button. Hold the 
button until both dots in the display start to blink.

 

The display indicates 

 0.0.

.

 

Deactivate manual mode by pressing the On/Off 
button.

 

After 5 minutes in manual mode, the PFA  switches 

back to normal operation automatically.

When using operating mode parameters set at the 

factory
PFA 700, PFA 70

Parameter 43 = 1

 4 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 04

.

 

The PFUs start the burners and open the air valve 

via the external control system (programming of the 
operating mode at the factory).

When using adjusted operating mode parameters
ON/OFF operating mode
PFA 700 in conjunction with PFU 760

Parameter 43 = 2

 4 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 03

.

 

The PFUs start the burners.

 5 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 00

.

 

The PFUs switch off all the burners.

 

By pressing the Reset/Information button repeatedly, 
the PFUs are activated to switch between burner start 
(the display indicates step 

 03

) or burner off (the display 

indicates step 

 00

).

PFA 700 in conjunction with PFU 760..L

Parameter 43 = 3

 4 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 01

.

 

The PFUs start the burner pre-purge procedure.

 WARNING

The pre-purge duration is not included in the program. 

Pre-purge until the combustion chamber has been ad-
equately ventilated.

 5 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 03

.

 

The PFUs start the burners.

 6 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 00

.

 

The PFUs switch off all the burners.

 

By pressing the Reset/Information button repeatedly, 
the PFUs are activated to switch between pre-purge 
(the display indicates step 

 01

), burner start (the display 

indicates step 

 03

) or burner off (the display indicates 

step 

 00

).

Содержание BGT SA-8U/1DP

Страница 1: ...NING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 06 13 The following chapters have been changed BGT SA 9U 1D...

Страница 2: ... Part designations 2 6 1 3 4 6 7 5 8 1 LED display for program status and error messages 2 Reset Information button 3 On Off button 4 Type label 5 Connection for opto adapter 6 Screws for attachment to the subrack 7 Code switches for address setting 8 CD with device master data GSD file Input voltage and ambient temperature see type label PFA 700 BGT SA 9U 1DP Pre wired module subrack for a fieldb...

Страница 3: ...ram Setting the PFA All the unit specific parameters for the PFA are saved in a device master data file GSD file see www docutheck com 1 Copy device master data for the PFA into the program mable logic controller PLC The steps required to copy the file are described in the instructions for the PLC 2 Configure the PROFIBUS DP using the appropriate tools for the PLC you are using The PFA will automa...

Страница 4: ... A P DI on on on PFU 7 2 3 3 4 1 2 PFU 2 1 2 PFU 4 1 2 PFU 6 1 2 PFU 8 4 5 1 2 PFU 2 1 2 PFU 4 1 2 PFU 6 1 2 PFU 8 1 2 ϑ A P A P DI on on on PFA 6 1 2 ϑ A P A P DI on on on PFU 2 1 2 ϑ A P A P DI on on on PFU 4 1 2 ϑ A P A P DI on on on PFU 6 1 2 ϑ A P A P DI on on on PFU 8 7 Legend 1 2 ϑ A P A P DI on on on Ready for operation 1 2 ϑ A P A P DI on on on Burner start up signal 1 2 Start up signal p...

Страница 5: ... in manual mode the PFA switches back to normal operation automatically When using operating mode parameters set at the factory PFA 700 PFA 710 Parameter 43 1 4 Press the Reset Information button for 1 s The display indicates step 04 The PFUs start the burners and open the air valve via the external control system programming of the operating mode at the factory When using adjusted operating mode ...

Страница 6: ...ers switch to low fire rate Each time the Reset Information button is pressed the air valves are opened the burners switch to high fire rate the display indicates 04 or closed the burn ers switch to low fire rate the display indicates 03 PFA 710 in conjunction with PFU 780 L Parameter 43 4 4 Press the Reset Information button for 1 s The display indicates step 01 The PFUs start the burner pre purg...

Страница 7: ...al mode Switch the PFA to normal operation The display indicates Profibus module fault Remove the unit and return it to the manufacturer The display indicates 30 31 34 80 89 94 95 96 97 98 or 99 Internal faults Remove the unit and return it to the manufacturer Technical data BGT Weight 2 3 kg PFA Front width 8 depth units 40 6 mm Overall height 3 height units 128 4 mm Ambient temperature 20 C to 6...

Страница 8: ...2e 4e 2c 4c sk1 PFU 7xx v2 v1 6a 6e c1 c2 10c 12c 10a 12a 30e 22a 2 1 1 2 28c 26a 14a 14e 10e 12e 24c 20c 18a l Z I 1 26e 30a 32c 230 V F1 s PFU c1 c2 10c 12c 10a 12a 30e 22a 1 2 28c 26a 14a 14e 10e 12e 24c 20c 18a Z I 1 1 1 1 2 3 4 5 6 X9 7 8 DI 2 X10 21 X1 3 X1 5 UVS 1 2 3 X10 21 GB 8 GB F NL I E BGT SA 9U 1DP connection diagram ...

Страница 9: ...Vex 24 Vex 1 2 3 4 1 2 3 4 14b 18b 21b 22b 23b 24b I O 18c N PE 24 Vex 0 Vex 19b 20b 1 2 3 4 5 6 7 8 9 10 X10 11 12 13 30e 14 17 18 19 20 21 22 X10 K2 K1 COM k2 k3 k5 k4 E1 E2 E3 E4 P 30c PFU 19c 17b 24 V L1 PROFIBUS DP 25b 26b K4 K5 K3 24 Vex 24 Vex 24 Vex max 1 A 24 V PROFIBUS DP PFU 7xx 1 9 1 22e 16c 18e 2a 4a 2e 4e 2c 4c sk1 U 7xx v2 v1 6a 6e 2 1 l DI 2 15 16 1 2 3 4 5 6 X1 7 8 k1 GB 9 D GB ...

Страница 10: ... v2 v1 6a 6e c1 c2 10c 12c 10a 12a 30e 22a 2 1 1 2 28c 26a 14a 14e 10e 12e 24c 20c 18a l Z I 1 26e 30a 32c 230 V F1 s PFU c1 c2 10c 12c 10a 12a 30e 22a 1 2 28c 26a 14a 14e 10e 12e 24c 20c 18a Z I 1 1 1 1 2 3 4 5 6 X8 7 8 DI 2 X8 3 X8 5 UVS 1 2 3 X10 21 X1 3 X1 5 UVS 1 2 3 X10 21 GB 10 GB F NL I E BGT SA 8U 1DP connection diagram ...

Страница 11: ...b I O 17c N PE 24 Vex 0 Vex 19b 20b 1 2 3 4 5 6 7 8 9 10 X10 11 12 13 30e 14 17 18 19 20 21 22 X10 K2 K1 COM k2 k3 k5 k4 E1 E2 E3 E4 P 30c PFU 19c 17b 24 V L1 PROFIBUS DP 25b 26b K4 K5 K3 24 Vex 24 Vex 24 Vex max 1 A 24 V PROFIBUS DP PFU 7xx 1 8 1 22e 16c 18e 2a 4a 2e 4e 2c 4c sk1 U 780 v2 v1 6a 6e 2 1 l DI 2 15 16 1 2 3 4 5 6 X1 7 8 2 1 1 2 1b 1 PFU 7 PFU 7b 27a 8 PFU 27c 27b 24a 26a 1 PFU 2 PFU ...

Страница 12: ...ations to the Profibus bus ca ble To replace existing PROFIBUS plug connectors if a new PFA 700 is operated in an old module subrack with the Order No 84402283 in order to improve EMC see page 4 Replacing the PFA 5 5 15 A B A B O N O F F Data cable fold back the woven shield A and B incoming cables A and B outgoing cables 1st and last stations ON other stations OFF Data cables A and B must not be ...

Отзывы: