Krom Schroder valVario VAA 1 Скачать руководство пользователя страница 4

VAA · Edition 05.22

EN-4

Plug

 

LV1 (+) = black, N (–) = blue

 a 

 

 b 

(+)

LV1

N

(-)

socket

 

1 = N (–), 2 = LV1 (+)

 a 

 

 b 

 

 c 

 

 d 

 

 e 

2

1

Position switch

 

VAA open: contacts 

1

 and

2

 closed, 

 

VAA closed: contacts 

1

 and 

3

 closed. 

 

Indicator of position switch: red = VAA open, white 

= VAA closed. 

 CAUtIon

Please observe the following to ensure smooth 
operation:

 

– Route valve and position switch cables 

separately through M20 cable glands or use two 
separate plugs. Otherwise, there is a risk of 
interference between valve voltage and position 
switch voltage.

 

To make wiring easier, the connection terminal for 

the position switch can be removed.

1 3

2

LV1

(+)

N

(-)

1

COM

2

Valve open

Valve closed

3

1 3

2

LV1

(+)

N

(-)

1

COM

2

Valve open

Valve closed

3

 

When installing two plugs on VAA a with position 
switch: label the sockets and plugs to avoid con-
fusion. 

2

1

3

2

1

1

COM

2

Valve open

Valve closed

3

 

Ensure that the connection terminal for the position 
switch has been reconnected.

Finishing the wiring

 5 

5 settInG tHe BYPAss

The system can be operated at burner low-fire rate or 

purge air using a variable bypass.

The flow rate is adjusted individually using the scale 

on the bypass.

The bypass can be attached at the right- and/or left-

hand side of the flow body.

 

The bypass is set to the closed position (0°) at 

the factory.

 

We recommend to note the set opening angle on 
the type label.

Содержание valVario VAA 1

Страница 1: ...This unit must be installed and commissioned in accordance with the regulations and standards in force These instructions can also be found at www docuthek com 1 2 Explanation of symbols 1 2 3 a b c...

Страница 2: ...ent temperature enclosure inlet pressure and installation position see type label Elster GmbH Osnabr ck Germany Vxx XXXX 3 INSTALLATION CAUTION Incorrect installation Please observe the following to e...

Страница 3: ...ended tightening torques for the connection parts See page 10 12 Technical data f g 4 WIRING WARNING Risk of injury Please observe the following to ensure that no damage occurs Electric shocks can be...

Страница 4: ...on switch can be removed 1 3 2 LV1 N 1 COM 2 Valve open Valve closed 3 1 3 2 LV1 N 1 COM 2 Valve open Valve closed 3 When installing two plugs on VAA a with position switch label the sockets and plugs...

Страница 5: ...adjusted for maximum flow rate Q The markings on the cover cap can be used for coarse adjustment of the flow rate The cover cap can be rotated without changing the current flow rate Allen key 2 5 mm D...

Страница 6: ...ly 2 Close the gas supply 3 4 5 6 7 8 Remove the M20 cable gland or other type of connection VAA without proof of closure switch a b c VAA with proof of closure switch a b c d e VAA with damping unit...

Страница 7: ...nit 1 2 3 4 5 6 7 Open the gas solenoid valve and the gas supply VAA with proof of closure switch Depending on the design of the proof of closure switch one of the two enclosed seals must be inserted...

Страница 8: ...5 13 Switch on the solenoid actuator so that the guide pin becomes visible 14 15 Switch off the solenoid actuator The damping unit is lowered 16 17 M3 18 Open the air supply and switch on the power su...

Страница 9: ...on to the PE wire see page 3 4 Wiring 11 ACCESSORIES 11 1 Pressure switch for gas DG VC The pressure switch for gas monitors the inlet pres sure pu and the outlet pressure pd Monitoring the inlet pres...

Страница 10: ...essure cleaner and or cleaning products 12 2 Mechanical data Gas types clean air The air must be clean and dry in all temperature conditions and must not contain condensate Medium temperature ambient...

Страница 11: ...s been reached safety relevant products must be replaced Designed lifetime based on date of manufacture in accordance with EN 13611 EN 161 for VAA Type Designed lifetime Switching cycles Time years VA...

Страница 12: ...of the Disclosure Table China RoHS2 see certificates at www docuthek com 16 DISPOSAL Devices with electronic components WEEE Directive 2012 19 EU Waste Electrical and Electronic Equipment Directive A...

Отзывы: