Checking the usage

DL..K

For monitoring positive, negative or differential air or 
flue gas pressures.

This function is only guaranteed when used within the 

specified limits – see page 4 (Technical data). Any 
other use is considered as non-compliant.

Type code

Code

Description

DL

Pressure switch for air

3,3 –  40

Max. setting in Pa

K

With tube connection and hand wheel 

for adjustment

T

T-product

G

Gold contacts

 

-1 

-3

Electrical connection 

via AMP plugs 

via screw terminals

K 

T

Red/green pilot LED 24 V DC/AC 

Blue pilot lamp 120 V AC 

Blue pilot lamp 230 V AC 

Red/green pilot LED 230 V AC

W

Z-angle bracket

Part designations

1

2

3

4

 

1

   Upper housing section with cover

  Lower housing section

3

  Hand wheel

4

  M16 cable gland

Type label

Mains voltage, switching pressure, ambient tempera-
ture and enclosure: see type label.

Osnabrück, Germany

DL..K

 

Installation

 CAUTION

Please observe the following to ensure that the 
DL..K is not damaged during installation and op-
eration:

–   Condensation must not be allowed to get into 

the housing (if possible, install pipework with an 
ascending gradient). Otherwise, there is a risk of 
icing of condensation at subzero temperatures, 
the switching point shifting or corrosion in the 
device which can lead to malfunctions.

–   In the case of uneven ground, secure the pres-

sure switch to the mounting plate or air duct 
with only two screws on the same side in order 
to avoid subjecting the pressure switch to me-
chanical stress.

–   Protect the connections against dirt or moisture 

in the medium to be measured or the surround-
ing air. If necessary, install a filter.

–   When using silicone tubes, only use silicone 

tubes which have been sufficiently cured. Va-
pours containing silicone can adversely affect 
the functioning of electrical contacts.

–   In case of highly fluctuating pressures, install a 

damping nozzle.

 

Installation in the vertical or horizontal position, or 
upside down, preferably with vertical diaphragm. 
If installed in a vertical position, the switching 
point p

S

 will correspond to the scale value SK. 

If installed in another position, the switching 
point p

S

 will change and no longer correspond 

to the set scale value SK. Switching point p

S

 

must be checked.

p

s

 = SK

SK + 13 Pa 

[+ 0.052 "WC]

SK - 13 Pa 

[- 0.052 "WC]

 1 

  Install the DL using screws, a securing clip or an 

angle bracket.

66

 4,4
(0.14")

 ø 6,1
(ø 0.24")

(2.6")

2

2

2

 

Tube connection: Ø 6 mm (0.236").

 

Max. inlet presure p

max.

 = 5000 Pa (20 "WC).

Содержание DL K Series

Страница 1: ... limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Transport On receipt of the product check that the delivery is complete see Part designations Report any trans port dama...

Страница 2: ...erwise there is a risk of icing of condensation at subzero temperatures the switching point shifting or corrosion in the device which can lead to malfunctions In the case of uneven ground secure the pres sure switch to the mounting plate or air duct with only two screws on the same side in order to avoid subjecting the pressure switch to me chanical stress Protect the connections against dirt or m...

Страница 3: ... using the hand wheel and scale The switching pressure differs from the adjusted setpoint by a maximum of 15 when it has been set for increasing pressure and with a vertical diaphragm Type Adjusting range Pa Mean switching differential at min and max setting Pa Deviation from the switching point during testing pursuant to EN 1854 or by agreement min max min max DL 3 3K 20 330 8 20 7 Pa 15 DL 3 5K ...

Страница 4: ...V min 0 01 A to 48 V DC max 1 A DL KT 30 240 V AC 50 60 Hz 5 A resistive or 0 5 A inductive cos ϕ 0 6 DL KTG 30 V AC DC 0 1 A resistive or 0 05 A inductive cos ϕ 0 6 Ambient temperatures DL K 15 to 85 C 5 to 185 F DL KT 40 to 60 C 40 to 140 F Line entrance M16 1 5 cable diameter 4 5 to 10 mm Enclosure to IEC 60529 IP 54 Diaphragm tempered LSR diaphragm system Max inlet pressure pu or differential ...

Отзывы: