Krom Schroder CPS 1000 Скачать руководство пользователя страница 1

4.2.2.2 Edition 02.10

 www.docuthek.com

D

GB

F

NL

I

E

© 2008 – 2009 Elster GmbH

Please read and keep in a safe place

 Please read through these instructions 

carefully before installing or operating. Follow-
ing the installation, pass the instructions on to the 
operator. These instructions can also be found at 
www.docuthek.com.

Explanation of symbols
 • ,  1 ,  2 ,   

... = Action

 

= Instruction

Liability

We will not be held liable for damages resulting 
from non-observance of the instructions and non-
compliant use.

Safety instructions

Information that is relevant for safety is indicated in 
the instructions as follows:

 DANGER

Indicates potentially fatal situations.

 WARNING

Indicates possible danger to life and limb.

 CAUTION

Indicates possible material damage.

All interventions may only be carried out by qualified 
gas technicians. Electrical interventions may only be 
carried out by qualified electricians.

Conversion, spare parts

All technical changes are prohibited. Only use OEM 
spare parts.

Transport

On receipt of the product, check that the delivery is 
complete (see Part designations). Report any trans-
port damage immediately. 

Storage

Store the product in a dry place. Ambient tempera-
ture: see Technical data.

Operating instructions

Translation from the German

D

GB

F

NL

I

E

GB-1

Safety

Contents

CPS  00 – 000
CPS  0 – 4000

CPS  00 – 000  . . . . . . . . . . . . . . . . . . . . . . . . . 1
CPS  0 – 4000  . . . . . . . . . . . . . . . . . . . . . . . . . 1
Contents  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Checking the usage . . . . . . . . . . . . . . . . . . . . . 2
Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Adjusting the switching pressure p

S . . . . . . . . . . 

Wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 
Accessories  . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Tube set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Pilot lamp set . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
External adjustment . . . . . . . . . . . . . . . . . . . . . . 4

Z-angle bracket  . . . . . . . . . . . . . . . . . . . . . . . . . 4

Motor flange. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Declaration of conformity . . . . . . . . . . . . . . . . 4
Contact  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Содержание CPS 1000

Страница 1: ...limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Transport On receipt of the product check that the delivery is complete see Part designations Report any trans port damag...

Страница 2: ...ation Protect the connections against dirt or moisture in the medium to be measured and the surrounding air Avoid subjecting the CPS to strong or violent vi brations Condensation must not be allowed to get into the housing At subzero temperatures malfunctions failures due to icing can occur When using silicone tubes only use silicone tubes which have been sufficiently cured The switching pressure ...

Страница 3: ... 330 20 330 8 18 CPS 450 30 500 10 25 CPS 510 100 510 13 25 CPS 800 50 800 15 40 CPS 1000 100 1000 25 40 CPS 1100 100 1100 15 40 CPS 1600 400 1600 20 60 CPS 2400 200 2400 35 75 CPS 3000 250 3000 60 80 CPS 4000 500 4000 40 100 Wiring CPS silver contact 24 250 V AC I 0 05 5 A cos φ 1 I 0 05 1 A cos φ 0 6 CPS G gold contact 12 250 V AC I 0 01 5 A cos φ 1 I 0 01 1 A cos φ 0 6 12 48 V DC I 0 01 1 A If ...

Страница 4: ...switching pressure for the pressure switches CPS 300 CPS 1000 or CPS 3000 when the cover is closed 2 1 Order No 74916155 Z angle bracket For fast installation and removal of the CPS 330 4000 with diverse mounting options even with only one screw The angle bracket increases the distance between pressure switch and mounting plate Order No 74919824 Motor flange For space saving attachment of the pres...