Komfort Zone Kit #KZK-050

Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces

7

2.0  FRAMING AND CLEARANCES

Figure 2.1, KZK Clearance to Sprinkler

2.1  Clearance to Sprinkler

• 

In a situation where a sprinkler head is installed within the 

proximity to a #KZK discharge opening, the diagram below 

MUST be followed. 

• 

The distance between a sprinkler head and discharge opening 

cannot be less than 60" (1524mm) in length at every point from 

the origin of the discharge opening. You must also verify the 

sprinkler head sensor is set to the proper heat setting so it does 

not activate when the room heats up from the fireplace being 

operated normally.

• 

Please follow local building codes to determine what 

temperature setting is relevant for your installation. 

CEILING

SPRINKLER HEAD

60”

(1524mm) MIN

2

½

” 

(63mm)

MIN

Содержание KOMFORT ZONE KIT KZK-050

Страница 1: ...fan The warm air flow may be relocated to a position higher up the wall out the sidewalls or even to an adjacent room The result is much cooler wall temperatures above the fire place opening for loca...

Страница 2: ......

Страница 3: ...num 4 to attach to the unit where the cover plates are removed 1 KZK 410 is used for a 10 vent run If installing beyond 10 vent run you will need to order 1 KZK CPL KZK CPL is 4 5 couplers that connec...

Страница 4: ...Mfg Co Inc Kozy Heat Fireplaces Komfort Zone Kit KZK 050 1 2 Suggested Configurations Figure 1 3 KZK 050 Suggested Configurations KZK 050 FRONT WALL OUTLET KZK 050 REAR WALL OUTLET KZK 050 CORNER INS...

Страница 5: ...inimum clearance to combustibles around pipe The tubing that connects the plenum to the fireplace must be UL181 Class 0 approved air duct If you are mounting the plenum above the fireplace 10 or less...

Страница 6: ...ance around the air duct pipes must be maintained Use KZK 410 UL181 Class 0 Air Duct piping to connect the plenum s to the unit Hussong Mfg requires pipes to be listed as UL181 Class 0 Air Duct to con...

Страница 7: ...lowed The distance between a sprinkler head and discharge opening cannot be less than 60 1524mm in length at every point from the origin of the discharge opening You must also verify the sprinkler hea...

Страница 8: ...Inc Kozy Heat Fireplaces Komfort Zone Kit KZK 050 2 2 Framing Figure 2 2 Rough Opening Figure 2 3 Minimum Clearances for Plenum and Air Discharge to Ceiling Figure 2 4 Framing and Clearances 2 1 6 CEI...

Страница 9: ...COVER PANEL COMBUSTIBLE MATERIAL ALLOWED BOTTOM 19mm NON COMBUSTIBLE MATERIAL ONLY COMBUSTIBLE MATERIAL ALLOWED COMBUSTIBLE MATERIAL ALLOWED SEE IMAGE BELOW FOR ACCEPTABLE SCREW LOCATIONS Figure 3 1 M...

Страница 10: ...s installed in accordance to this manual AND the convection baffle is removed when using these combustible clearances 9 248mm 26 673mm 16 425mm NOTE THESE MANTEL CLEARANCES APPLY ONLY WHEN THE KZK DUC...

Страница 11: ...KZK 050 Combustible Wall Finish with Surround Combustible wall finish may be installed over cement board If surround is used the combustible wall finish must maintain a 3 4 clearance to the top finis...

Страница 12: ...mbustibles as listed see previous pages Fix the plenum to the framing using nails or screw through the top mounting bracket FIREBOX CONVECTIVE AIRFLOW WITH THE BAFFLE IN PLACE CONVECTION BAFFLE TO BE...

Страница 13: ...the plenum s may be visible 10 Install the KZK 050DT discharge trim to the plenum after the wall finish is completed using 2 screws if using the KZK 050 plenum Finishing material must not block and s...

Страница 14: ......

Страница 15: ...eut tre dirig e plus haut sur le mur travers les murs adjacents ou m me vers la pi ce adjacente Cela permet de r duire beaucoup la temp rature des murs au dessus du foyer pour pouvoir y in staller une...

Страница 16: ......

Страница 17: ...s 1 KZK 410 est utilis pour conduits d air de 10 pieds 3 05 m Pour installer des conduits de plus de 10 pieds 3 05 m il faut commander 1 KZK CPL KZK CPL inclut 4 coupleurs de 5 po qui raccordent 2 KZK...

Страница 18: ...nc Kozy Heat Fireplaces Kit Komfort Zone n KZK 050 1 2 Configurations sugg r es Figure 1 3 Configurations sugg r es du KZK 050 KZK 050 INSTALLATION DANS UN COIN KZK 050 SORTIE MURALE ARRI RE KZK 050 S...

Страница 19: ...gu s UL 181 Conduits d air de Classe 0 Si vous installez le pl num moins de 10 pieds 3 m au dessus du foyer utilisez un 1 kit n KZK 410 Si vous installez le pl num plus de 10 pieds 3 m et moins de 20...

Страница 20: ...oit tre maintenu Utilisez les conduits d air no KZK 610 homologu s UL 181 Conduits d air de Classe 0 pour raccorder le s pl num s au foyer Hussong Mfg exige des conduits d air homologu s UL 181 de Cla...

Страница 21: ...te de gicleur et l ouverture de sortie d air ne doit pas tre inf rieure 60 po 1 52 m en tout point mesur e partir de l ouverture de sortie d air Vous devez aussi v rifier que le d tecteur de la t te...

Страница 22: ...aces Kit Komfort Zone n KZK 050 ACIER D ENCADREMENT 6 22 ACIER D ENCADREMENT 4 2 2 Encadrement Figure 2 2 Ouverture brute Figure 2 3 D gagement minimal de la sortie d air au plafond Figure 2 4 Encadre...

Страница 23: ...NF RIEUR MAT RIAUX COMBUSTIBLES PERMIS MAT RIAUX INCOMBUSTIBLES SEULEMENT MAT RIAUX COMBUSTIBLES PERMIS MAT RIAUX COMBUSTIBLES PERMIS AUCUNE VIS N EST PERMISE AUCUNE VIS PERMISE 3 95mm AUCUNE VIS PERM...

Страница 24: ...nform ment ce manuel ET de retirer le d flecteur de convection si vous utilisez les d gagements aux mat riaux combustibles sp cifi s dans ce manuel 9 248mm 26 673mm 16 425mm Assurez vous d installer l...

Страница 25: ...dessus le panneau de ciment Si une contour optionnel est utilis mat riaux de finition murale combustibles tre maintenue 3 4 po d gag e jusqu au sommet de finition du foyer PLANCHER D ENCEINTE DU FOYE...

Страница 26: ...VECTION SANS LE D FLECTEUR combustibles tels que sp cifi s aux pages pr c dentes Fixez le pl num l encadrement avec des vis ou clous traversant la bride de fixation sup rieure NOTE Les brides de fixat...

Страница 27: ...ous utilisez le pl num du kit KZK 050 Les mat riaux de finition ne doivent pas boucher l ouverture de sortie d air du pl num mais doivent border uniform ment tout le pourtour de l ouverture de sortie...

Страница 28: ......

Отзывы: