background image

CAUTION

BEFORE INSTALLING THE AIR CONDITIONER, IT IS IMPORTANT THAT THESE INSTRUCTIONS BE READ AND UNDERSTOOD THOROUGHLY

KOOLTRONIC, INC. 30 Pennington-Hopewell Road Pennington, NJ 08534 

609 • 466-3400 FAX: 609 • 466-1114

kooltronic.com

900-090-83 (11/18)
(CDR: 20111)

Installation Instructions

Model KA4C3DP21L

with Serial Numbers L18A3965 and above

I. Introduction

These instructions provide you with the general information necessary for proper installation of the air conditioners.

II. Incoming Inspection

Kooltronic Air Conditioners are designed, built and packaged to withstand the shock and vibration normally associated with shipment by common carriers. Occasionally
improper  handling during shipping causes damage. Such handling could include unbanding of palletized shipments, failing to respect 

"This Side Up"

arrows, rough

handling, falling off conveyors, excessive vibration, crushing, etc. Therefore, a thorough inspection should be done upon receipt of all shipments. Any carton tears, dents,
scratches, loose articles or evidence of oil are signs of damage and should be noted on the Freight Bill. Cartons should be opened promptly and the units inspected for
CONCEALED DAMAGE. Kooltronic Air Conditioners must be delivered in the proper mounting position to assure that damage to the compressor has not occurred during
shipping. Any Kooltronic Air Conditioner that is delivered removed from the banded pallet, lying down or double stacked should be refused.

An immediate claim MUST be filed with the freight carrier and an inspection requested. Retain all packing materials. Kooltronic cannot assume responsibility for Consignee's
failure to file a timely freight claim.

Kooltronic Air Conditioners must be operated in their proper mounting position. If attempts are made to operate a unit that is not in its designed
mounting position, permanent compressor damage will occur. This action will void the warranty. 

If the air conditioner is mounted to the cabinet door you must be sure that the door hinges will support the additional weight of the air conditioner.
Also be certain that when the door is opened fully, the cabinet does not become unbalanced. The weight of the unit is 45 lbs. Additional technical
data can be found in the performance specifications in the Operator’s Manual available online.

CAUTION

Kooltronic Air Conditioners must be standing in their proper mounting position for a minimum of five (5) minutes prior to testing. Failure to
follow this procedure will cause permanent damage to the compressor. To avoid compressor damage do not tip the unit more than 45° from
its proper mounting position

IV. Mounting

External Mounting

1.

Place the supplied 

1/

2

-inch gaskets on the two evaporator side cutouts as shown in the gasket drawing on next page. The

gaskets must start and end at the middle bottom of the cutouts. The gaskets must remain as one continuous piece around
the cutouts. Bend gaskets around the corners. Do not stretch the gaskets.

2.

It is recommended that a lift truck be used for installation.

3.

Attach the Mounting Plate to the enclosure using (3) 

1/

4

-inch nuts, (3) sealing washers as a spacer and (3) 

1/

4

-inch 

mounting nuts. Note that the mounting plate is not symmetrical. Be sure to install with the longer section at the top and 
the shorter section at the bottom. Sealing washers must be placed against customer enclosure (see External Mounting 
Drawing and Mounting Plate Detail).

4.

Place the air conditioner on the lift truck. Insert a 1-inch (approximate) wooden block between the lift truck bottom and the
air conditioner bottom so that the angle between the unit mounting panel and the air conditioner is about 10 degrees.

5.

Adjust the lift truck height so that the air conditioner hook is located approximately 

1/

2

-inch above the mounting plate.  

6.

Route the power cord through the discharge (upper) air cutout.

7.

Move the air conditioner toward the enclosure panel so that the gap between the hook and the enclosure is about 

1/

2

-inch. 

8.

Slowly move the lift truck down until the hook engages with the mounting plate. Continue to lower the lift truck. The air 
conditioner will hang from the mounting plate flush against the mounting panel.

III. Pre-Installation Testing

1.

The unit must sit in an upright position at a minimum room temperature of 65°F to allow the system to warm-up. This is particularly important during winter months.

2.

Refer to the identification label for proper electrical voltage and current requirements. Connect the power cord to a properly grounded and fused electrical supply,
leaving electrical power to the unit turned off.

3.

Note the factory thermostat setting which is 75°F.

4.

Turn the electrical power on. Verify that the evaporator blower or fan is running. Verify that the condenser fan is running.

5.

Observe the temperature on the digital display. The thermostat must be set a minimum of 10ºF below this
temperature for the compressor to operate (the factory setting is 75ºF). To set the thermostat temperature: 1) Press
SET for 3 or more seconds. 2) Use UP or DOWN arrows to set the temperature. 3) Press SET again.

6.

Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise or vibration should be
evident. Both the evaporator and condenser fans or blowers should be delivering air through their respective discharge
ports. The cool air discharged should be less than 70ºF when the room temperature is between 70ºF and 80ºF.

7.

Turn off the electrical power and disconnect the air conditioner from the power source. 

8.

If any cover plug was removed to adjust the unit, be sure to replace it in order to maintain the integrity of the closed-loop
airflow system. 

Internal Mounting

1.

Place the supplied 

1/

2

-inch gaskets on the two condenser side cutouts as shown in the gasket drawing on next page. 

The gaskets must start and end at the middle top of the cutouts. The gaskets must remain as one continuous piece 
around the cutouts. Bend gaskets around the corners. Do not stretch the gaskets.

2.

Remove the three #10 screws together with rubber washers from the Rear Panel top.

3.

Attach the supplied mounting angle to the Rear Panel top with the three #10 screws and rubber washers (see Internal 
Mounting Drawing).

4.

It is recommended that 

1/

4

-inch x 1

1/

4

-inch mounting studs be used on the customer enclosure door or panel. If not, 

use the hardware supplied for air conditioner mounting.

INTERNAL MOUNTING DRAWING

MOUNTING BRACKET

1/4'' NUT (3)

 

ENCLOSURE

      WALL EXTERIOR

         TOP SECTION 

       OF A/C UNIT

         BOTTOM SECTION 

OF A/C UNIT

RUBBER WASHER (3)

 

1/4'' BOLT OR STUD (3)

RUBBER WASHER (3)

1/4'' BOLT OR STUD (3)

1/4'' NUT (3)

EXTERNAL MOUNTING DRAWING

INSTALL THE MOUNTING PLATE W/STUDS 

    TO THE OUTSIDE WALL OF THE CUSTOMER'S 

 ENCLOSURE BEFORE INSTALLING A/C UNIT.

NOTE:

ENCLOSURE WALL

TYP. (3) PLACES

1/4'' NUT

 CUSTOMER'S 

ENCLOSURE

TYP. (3) PLACES

BOLT 1/4'' X 1-1/4''

RUBBER WASHER

MOUNTING PLATE 
WITH STUDS 
(SEE DETAIL 
AT RIGHT)

TOP SECTION 

       OF A/C UNIT

BOTTOM SECTION 
OF A/C UNIT

RUBBER WASHER

1/4'' NUT

1/4'' NUT

TIGHTEN NUT TO 

CLOSE GAP

Отзывы: