background image

Keep This  Manual

With Air Conditioner

AIR CONDITIONER

OPERATOR'S MANUAL

CAUTION

BEFORE INSTALLING AND

USING THIS AIR CONDITIONER,

IT IS IMPORTANT THAT THIS

MANUAL BE READ AND

UNDERSTOOD THOROUGHLY

KOOLTRONIC, INC.

30 Pennington-Hopewell Road

Pennington, NJ 08534

609 • 466-3400

FAX: 609 • 466-1114

www.kooltronic.com

TRIMLINE

NP59 and TP59

SERIES

900-039-09 (2/19)
(CDR: 20131)

Содержание K2A3C14NP59R

Страница 1: ...FORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 46...

Страница 2: ...tion Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronic enclosures...

Страница 3: ...e in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operati...

Страница 4: ...ements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent dam...

Страница 5: ...by means of the vapor compression refrigeration cycle This takes place in a hermetically sealed refrigeration system utilizing either an air cooled or water cooled condenser heat exchanger The warm ai...

Страница 6: ...delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and cond...

Страница 7: ...supplied by Kooltronic 1 4 20 screws nuts washers NOTE Make sure the screws are inserted with heads on M TAB side Tighten nuts securely 5 Route the power cord through the top cut out in your cabinet M...

Страница 8: ...l or exceed size of cool air outlets FILTERED CONDENSER AIR INLET Ambient Air In CONDENSER OUTLET Warm Ambient Air Out COOL AIR OUTLET TO ENCLOSURE Drawings and Dimensions NP59 and TP59 SERIES 8 Other...

Страница 9: ...chable Switch is internally mounted for security Rating shown is for operation at maximum ambient temperature 115V 60 Hz and 230V 60 Hz models also perform at full capacity when operated at 100V 50 Hz...

Страница 10: ...REASE CLOSES ON PRESS RED TO YELLOW COMMON RED BLUE YELLOW CRANKCASE HEATER PRESSURE SWITCH N O OPTIONAL YELLOW BLUE RED h COMMON RED TO YELLOW CLOSES ON TEMP INCREASE RED TO BLUE OPENS ON TEMP INCREA...

Страница 11: ...Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet f...

Страница 12: ...valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refri...

Страница 13: ...ntrol Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Appli...

Страница 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...