Maintenance Manual
KONGSBERG PROPRIETARY.
This document and its accompanying elements contain KONGSBERG
information which is proprietary and confidential. Any disclosure, copying, distribution or use is prohibited if not
otherwise explicitly agreed with KONGSBERG in writing. Any authorized reproduction, in whole or in part, must
include this legend. ©2022 KONGSBERG - All rights reserved.
P a g e
37 |
73
Cleaning of Water/Oil Cooler
Clogging will reduce the heat transfer capacity of the Water/Oil cooler.
Methods for establishing a clogging problem:
•
Check water inlet and outlet temperature. Clogging results in reduced difference in water inlet
and outlet temperatures and a rise in oil temperature.
•
Check for a pressure drop across the cooler. Clogged and narrow passages will cause
acceleration in flow rate and increased pressure drop.
If temperature or pressure measuring reveals a clogged cooler:
1.
Clean the Water/Oil cooler by removing all minor deposits by back flushing the cooler with
water.
Fouling can be dealt with using a light acid.
2.
Use 5% phosphoric acid or, when cleaned frequently, 5% oxalic acid or similar light organic acid.
3.
Rinse the cooler with a large quantity of water.
Note!
Make sure all acids are removed before restarting the system.