AKD2G-S Installation Manual, Safety 1 | 8 Electrical Installation
8.8 Regen resistor (X3)
For technical data on the regenerative brake circuit (
Fusing (such as fusible cut-outs or power switches) to be provided by the user.
8 pin, pitch 7.62 mm
optional T version
Mating connector data (
X3/5 to X3/6 must be shorted to use the built in regen resistor.
Remove the jumper to connect an external regen resistor .
Refer to the WorkBench online help for parameter setting
(REGEN.EXT, REGEN.REXT, REGEN.WATTEXT)
Pin
Label
Signal
Description
5
Ri
RBint
internal Regen resistor
6
Re
-RB
external Regen resistor -
7
+DC
+RBext
external Regen re
8.8.1 Fusing and Wiring
FB1 / FB2 fusing
Drive Model
Ampere
rating@240V
Ampere
rating@480V
UL region
example:
CE Region
example: Siba
all AKD2G-Sxx
10A
40A
Eaton
FWP-xxA14F
110V to 400V: gRL(gS)
400V to 480V: aR
FPS: Frizlen DC Power Switch
RBext
FPS
Range [In]
cable cross section
BAR(U)1500-33
FPS-16
10 to 16 A
min. 2.5 mm²
78
Kollmorgen | kdn.kollmorgen.com | July 2020