7 Enable PWM Output on RS485 I/O
These steps use both WorkBench and MotionConsole.
Enable the Pulse Width Modulation (PWM) output on an RS-485 I/O using the following steps:
The PWM output is not available on the opto-isolated DOUT1 and DOUT2 because these outputs are too
slow to be useful.
1. Set DRV.EMUEMODE parameter in WorkBench to 10 - General Purpose I/Os.
2. Set DOUT9.DIR in WorkBench to 1-Output.
For SynqNet:
DOUT9.INV forced to 0 (SynqNet controls output polarity)
DOUT9.MODE forced to 0 (SynqNet controls output source)
3. Open MotionConsole.
AKD SynqNet | 7 Enable PWM Output on RS485 I/O
Kollmorgen | kdn.kollmorgen.com | October 2020
21