AKD-C Installation | 9 Electrical Installation
9.5 Wiring
DANGER
High Voltage up to 900 V
There is a danger of serious personal injury or death by electrical shock or
electrical arcing.
Only install and wire the equipment when it is not live, that is, when
neither the electrical supply nor the 24 V auxiliary voltage nor the sup-
ply voltages of any other connected equipment is switched on.
Make sure that the cabinet is safely disconnected (for instance, with a
lock-out and warning signs). The individual voltages are switched on
for the first time during setup.
Only professional staff who are qualified in electrical engineering are allowed to install the
decentral drive system. Wires with color green with one or more yellow stripes must not be
used other than for protective earth (PE) wiring. When installing or replacing cables, use only
standardized components, which complies to the specifications in chapter 7.10 "Cable
Requirements".
The ground symbol, which you will find in the wiring diagrams, indicates that you must take
care to provide an electrically conductive connection with the largest feasible surface area
between the unit indicated and the mounting plate in the control cabinet. This connection is
for the effective grounding of HF interference, and must not be confused with the PE-symbol
(PE = protective earth, safety measure as per IEC 60204).
Use the following connection diagrams:
Overview AKD-C
Mains supply
24 VDC supply
DC bus link
Drive string connection
Digital I/O
Motion Bus
Service interface