KWV-20G*ATA**

REV — 02/26/20

UNIT COMPONENTS

Optional Deflection Registers

The supply grilles are divided into 2 rows of 

manually adjustable louvers.
The horizontal louvers are in the front row. These 

are individually adjusted by hand.
The vertical louvers are the second or back row. 

Each section has a louver adjustment tab. The 

tab will adjust the vertical louvers as a section and 

can be moved with your finger.

Optional Hour Meter

The unit may be equipped with an optional 

hour meter. This meter indicates the cumulative 

operating time of the system.

Sight Glass

Each refrigerant circuit has a sight glass to 

determine that a liquid seal of refrigerant exists 

going to the expansion valve. 
The sight glass also has a moisture indicator to 

detect the presence of moisture in the refrigerant.  

The indicator is yellow if moisture is present and 

green in color if there is no moisture.
If bubbles appear in the sight glass, the system is 

either undercharged with refrigerant or there may 

be a restriction in the liquid line upstream of the 

sight glass.

NOTE:

  Bubbles will occur for a minute or two 

when the compressor system starts. 

Bubbles will also be present during low 

ambient operation or on the 20-ton unit 

circuit 1 when the hot gas bypass is 

activated. Do not add charge to overcome 

bubbles for these reasons.

Access Fittings

Each refrigerant circuit is provided with Schrader 

type access fittings. These can be used to adjust 

the refrigerant charge if necessary.

Air Flow

The units are provided with an air proving switch. 

If air flow is not detected, the unit will not allow 

the cooling circuit to function. This protects in the 

case of a motor or belt failure.

Pressure Switches

Each refrigerant circuit is provided with a High 

and a Low pressure switch. These are automatic 

reset type.
These units contain lockout relays that activate 

when the pressure switch(s) open the circuit. The 

main power to the unit must be switched Off and 

then On to reset the lock out relays

CAUTION:  Unit power should be turned off 

when doing any work on the unit 

when one or both of the pres-

sure switches has been opened . 

Unit may start when the pressure 

switches automatically reset, thus 

causing a hazard to the service 

personnel .

Hot Gas Bypass

20-ton units have a Hot Gas Bypass valve on 

System 1.  This valve helps keep the system 

running when the space load drops.  It functions 

by artificially loading the evaporator with some hot 

discharge gas from the compressor into the inlet 

of the evaporator. 

MAINTENANCE

Bearings

Motor and Blower bearings are permanently 

lubricated and require no maintenance.

Belts

The condenser and evaporator blowers are belt 

driven and are provided with adjustable sheaves 

to change the speed. The drive belts should be 

examined periodically for wear and for correct 

tension. If the belts are too tight it can cause 

Содержание KWV-20

Страница 1: ...26 20 Portable Air Conditioners Model KWV 20 SETUP OPERATION AND MAINTENANCE MANUAL 20 TON PORTABLE VERTICAL AIR CONDITIONING UNIT 260 North Elm St Westfield MA 01085 Phone 413 564 5520 Fax 413 564 58...

Страница 2: ...CYCLE 60 COMP LRA 351 EA QTY 2 RLA 53 6 EA EVAP MOTOR HP 15 0 FLA 35 COND MOTOR HP 3 0 EA QTY 2 RLA 8 6 EA ELEC HEATER KW 60 MCA 240 8 MOP 250 FACTORY CHARGE R 410A 46 lb 0oz CKT1 46 lb 0oz CKT2 TEST...

Страница 3: ...unding wires screws straps clips nuts or washers used to complete a path to ground are removed for servicing they must be reconnected at their original location TABLE of CONTENTS IDENTIFICATION OF YOU...

Страница 4: ...hp Voltage Phasing Frequency 208 3 60 FLA Amps 13 6A Design Condenser Air Flow 12 400 CFM EVAPORATOR BLOWER MOTOR Horsepower 5 hp Voltage Phasing Frequency 208 2 60 FLA Amps 13 6A Evaporator Design Ai...

Страница 5: ...nd is required 5 Refer to the unit data plate for main power re quirements Electrical wiring and grounding must be installed in accordance with the latest revision of the AS NZS 3000 standard Route th...

Страница 6: ...all be used to control the conditioning of the air Select Manual Cool when 1 to 2 stages of Manual Cooling is are desired Select Manual Heat when 1 to 2 stages of Manual Heating is are desired If Manu...

Страница 7: ...these reasons Access Fittings Each refrigerant circuit is provided with Schrader type access fittings These can be used to adjust the refrigerant charge if necessary Air Flow The units are provided w...

Страница 8: ...hort Cycling Single Phase units have a time delay relay that delays the start of the compressor for 5 minutes when there is a call for cooling Each single phase unit must have a time delay relay for c...

Страница 9: ...into the evaporator As the liquid enters into the expansion valve the valve will start to change the state by changing the pressure of the liquid refrigerant as it passes through and starts to enter...

Страница 10: ...erably or even premature motor failure as well Belt Span is the distance in inches between the drive shaft center point and the fan shaft center point Refer to Figure 7 Belt Tensioning below Figure 7...

Страница 11: ...ait one hour to see if it resets and starts 7 Defective compressor valves Replace compressor 8 Reset the overload and also check and reset the high pressure switch if required High Pressure Trips 1 Co...

Страница 12: ......

Отзывы: