Air Heater Termis

INSTALLATION, USE AND MAINTENANCE

The Air Heater Termis is designed for in-

door use. The ambient temperature shall 

be 0…40°C if water is used as the heat 

transfer fluid. 

The air to be heated must not be corrosive 

or contain large quantities of water vapour 

or large particles.

Installation

The air heater is installed fixed on the wall by means of 

mounting brackets (accessory).

Fix first the brackets at the desired height on the wall,   

select fixing screws according to the wall material. Make 

sure that the brackets are at the same height.

Loosen the fixing screws of the air heater and lift the 

air heater by the lower corners onto the brackets. Tighten 

the fixing screws.

NB! Do not lift the air heater by the fittings of the heat 

exchanger, fan or grille. 

Connection to the heating system

Connect the inlet pipe to the lower pipe fitting and the out-

let pipe to the upper pipe fitting by using suitable clamps.

Max operating pressure is 1.0 MPa and temperature  

150°C.

Fill the heat exchanger with water and vent the system.

Electrical connection

The  air  heater  is  connected  according  to  the  diagram 

below,  transformer  regulator  is  available  as  an  acces-

sory. Only an authorized electrical installation company 

is allowed to connect the air heater.

Test  the  air  heater  and  make  sure  that  the  impeller 

rotates in the right direction.

Standard  products  are  one-phase,  three-phase  air 

heaters are available by special order.

Termis 35 ja 45

Termis 56

3-phase

1-phase

3-phase

1-phase

black

gray

blue

red brown

orange

violet violet

balck

blue

brown

black

green blue white brown yellow