Symptoms
Probable Cause
Possible Remedy
Outlet temperature too
cool (Continued)
Inlet water supply pressures are
unstable or imbalanced
Ensure the water supply pressures
are stable and nominally equal, refer
to
“Specifications”.
Outlet pipe run is too long
Ensure outlet pipe work is thermally
lagged.
Digital Mixing valve failure
Contact Rada.
Outlet temperature is
too hot or fluctuates
Temperature adjustment set too
high
Decrease temperature control -
Some models only.
Blend temperature set too high
Re-commission blend temperature
using the
“RADA AP1”
.
Hot inlet water supply
temperature is too hot
Reduce hot inlet water temperature
to between 55 °C and 65 °C, refer to
“Specifications”.
Inlet filters or check valves
blocked
Check and remedy.
Outlet spout, hose or handset
blocked
Check and remedy.
Reversed inlet supplies
Check and remedy.
Fluctuating supply pressures and
/ or temperatures
Check and remedy.
Inlet water supply pressures are
unstable or imbalanced
Ensure the water supply pressures
are stable and nominally equal, refer
to
“Specifications”.
Temperature affected by use
of adjacent hot/cold outlet.
Insufficiently sized pipe work to
feed both Digital Mixer Valve and
additional outlets at the same time.
Increase pipe sizes or separately
feed to the product.
Digital Mixing valve failure
Contact Rada.
No shut off / Continuous
flow
Run on time set too long
Check settings in the
“RADA AP1”
.
Possible debris in Digital Mixing
Valve
Power cycle the digital mixer (turn off
and on again). Ensure inlet filters are
clean.
Perform a cold flush using the Coms
App to flush debris from unit.
Digital Mixing Valve failure
Contact Rada.