5.3.3 How to transfer to on-line (on inverter) from ECO (on bypass) mode
The UPS can be manually switched to on-line (on inverter) from the ECO (on bypass) mode using the module control
panel load transfer menu.
1. On the module control panel (of any UPS module) press the
ENTER
key once to access the menu system.
2. Using the
UP/DOWN
keys, move the cursor so that it is adjacent to
COMMANDS
and then press the
ENTER
key.
3. Using the
UP/DOWN
keys, move the cursor so that it is adjacent to
LOAD
TO
INVERTER
and then press the
ENTER
key.
a) The UPS system will transfer the load to the static bypass (on all UPS modules in a parallel-module system).
4. On the module control panel(s), verify that:
a) The
INVERTER
LED is green.
b) The
BYPASS
LED is extinguished.
c) The LCD displays
LOAD PROTECTED
.
5.3.4 How to Turn OFF the UPS system when operating in ECO (on bypass) mode