TS_616_08 PW8000DPA ST (S2) User Manual 21/4/22
4
Installation
4.1
Introduction
This chapter contains essential information concerning the unpacking, positioning, mechanical installation and cabling of
the PowerWAVE 8000DPA ST UPS.
4.2
Taking receipt of the UPS
The UPS cabinet(s) and accessories are delivered on purpose designed pallets that are easy to off load and move using a
forklift or suitable pallet jack.
Depending on the shipping method, the UPS is wrapped
in film or packed in either a cardboard or wooden
container designed to protect it from mechanical and
environmental damage.
Before you accept the shipment you should ensure that
the received package(s) correspond to the description
shown in the delivery documentation. Note that some
optional equipment packages might be shipped inside the
UPS container.
Upon receiving the UPS you should carefully examine the
packing container for any sign of physical damage.
External ‘TiltWatch’ indicators (2 off) will indicate RED if the equipment has been tilted during transportation.
4.2.1 Reporting transportation damage
If the ‘TiltWatch’ indicators are red or there are other signs of suspected transportation damage you must inform both the
carrier and Kohler Uninterruptible Power Ltd. immediately. Claims for shipping damage must be filed immediately when
found, and the carrier must be informed of ALL claims within seven days of receipt of the equipment. If the equipment is to
be stored for longer than seven days before it is installed, you should unpack it and inspect it for signs of internal damage
before you put it into storage. Any optional equipment packages that are shipped inside the main UPS package should
also be inspected.
If the equipment is damaged you should store the packing materials for further investigation.
WARNING:
All cabling operations must be supervised by an authorised electrician or other suitably
qualified person. All installation procedures must be carried out in strict accordance with the instructions
contained in this manual. Kohler Uninterruptible Power Ltd. will take no responsibility for any personal injury
or material damage caused by the incorrect installation, cabling or operation of this product.
WARNING:
Once the UPS equipment is installed it must be commissioned by an engineer approved by
Kohler Uninterruptible Power Ltd. before it is powered-up. Kohler Uninterruptible Power Ltd. will take no
responsibility for any personal injury or material damage caused by the application of electrical power to
this equipment before it has been fully commissioned and handed over to the customer.
CAUTION:
Observe the following precautions when off-loading and moving the UPS:
• Always keep the packages in an upright position.
• Do not drop the equipment.
• Due to the high-energy batteries involved and heavy weight, do not stack the pallets.
WARNING:
If the TiltWatch indicators indicate that the UPS has been tilted in transit DO NOT connect the
UPS to the mains electricity supply.
Figure 4.1 Tiltwatch indicators
Good
Bad
Содержание PowerWAVE 8000DPA RI (S2) Series
Страница 1: ...User Manual PowerWAVE 8000DPA ST S2 10 20 kVA kW Parallelable up to 400 kVA kW...
Страница 2: ...TS_616_08 PW8000DPA ST S2 UK User Manual 21 4 22...
Страница 4: ...TS_616_08 PW8000DPA ST S2 UK User Manual 21 4 22...
Страница 8: ...IV TS_616_08 PW8000DPA ST S2 UK User Manual 21 4 22...