3: Installation Planning
40
TS_616_08 PW8000DPA ST (S2) User Manual 21/4/22
Figure 3.8 Dual input cabling with common battery
UPS CABINET CONNECTIONS
UPS Module
ST-40
ST-60
ST-80
ST-120
ST-200
Load (kW)
40 kW
60 kW
80 kW
120 kW
200 kW
Input mains Fuse A (Agl/CB)
3x 80A
3x 125A
3x 160A
3x 224A
3x 350A
Input mains Cable (A)
Max input current, including max battery charging
68A
102A
136A
208A
333A
Bypass mains Fuse B (Agl/CB)
3x 80A
3x 125A
3x 160A
3x 224A
3x 350A
Bypass mains Cable B, max bypass current
58A
87A
116A
174A
290A
UPS output Cable D nominal current
58A
87A
116A
174A
290A
Battery Fuse F (Agl/CB) (with common battery only)
Bespoke to installation
IA-1 (MBP)
Fuse D
Cable D
Load
Fuse A
Fuse
F
Cable A
Input Mains
EARTH
PE
EARTH
PE
Sta c
Switch
DC/DC
Conv
Module 1
F4-1
Rect.
Inv.
Sta c
Switch
DC/DC
Conv
Module 2
F4-2
Rect.
Inv.
Sta c
Switch
DC/DC
Conv
Module 3
F4-3
Rect.
Inv.
Sta c
Switch
DC/DC
Conv
Module 4
F4-4
Rect.
Inv.
UPS CABINET
Fuse
B
Cable B
Bypass Mains