Controller Troubleshooting
TP-5672 11/95
Plant Exerciser
The Plant Exerciser is an accessory which periodically
tests the emergency source for proper operation. To
enable this option, the PLANT EXER jumper must be
installed on the logic board. See Figure 4-15. The
accessory is available in three different variations.
D
DD-23-C. Allows test of the engine generator set
only. The generator set will start and run under no
load.
D
DD-23-D. Allows a complete test of the emergency
source. The exerciser simulates a loss of normal
power. The generator set starts and the transfer
switch transfers the load to the generator set.
D
DD-23-G. Allows the customer to choose between
DD-23-C and DD-23-D with a Load/No Load
selector switch.
Option DD-23-C (no-load exerciser) and DD-23-D (load
exerciser) are wired differently. In order to enable
DD-23-D, TB-DC1-10 must be jumpered to TB-DC1-32.
See Figure 3-1 or 3-2.
The plant exerciser is programmed in Index 8. The
following information is needed to program the plant
exerciser.
D
Start time
D
Day of the week
D
Run time in hours and minutes
D
Week of the month (Calendar Mode Only)
Enter the information and enable the event to operate the
plant exerciser.
If the plant exerciser is programmed and functioning, the
Accessory Active, Plant Exerciser LED lights whenever
the plant exerciser is operating.
The Plant Exerciser uses three different modes.
D
7 Day. The timer looks at only 7 days at one time
D
14 Day. The timer looks at 14 days at a time
D
Calendar. The timer looks at a true calendar for
each month.
See Figure 4-27 through Figure 4-30 for troubleshooting
flowcharts for these options.
TB--DC1
MICROCONTROLLER
TB--AC1
Programming shunt (294634)
must be installed
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
17
ECS
EAS
NCS
NAS
LC
LB
LA
EC
EB
EA
NC
NB
NA
OVRIDE
DELAY
EXER
FREQ
SEQUENCER
MONITOR
MANUAL
TIME
PLANT
VOLT/
PHASE
IN--PHASE
NA
NB
NC
EA
EB
EC
LA
LB
LC
NAS
NCS
EAS
ECS
17
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
TB--AC1
MICROCONTROLLER
TB--DC1
560452
DELAYS
OFF
DD-23-C
DD-23-D
Jumper
Figure 4-25. Wiring Diagram— Plant exerciser, option DD-23-C and DD-23-D