TP-6694
9/20
49
Speed Sensor Fault.
The fault lamp illuminates yellow and the alarm horn sounds when the speed signal is absent for one
second while the generator set runs. The local display shows
Spd Sens Flt Warning.
2.4.6
System Fault Shutdown Lamp with Digital Displays
The system FAULT lamp glows red, the alarm horn sounds, and the unit shuts down to indicate a fault shutdown under the
following conditions. See the section titled: Controller Resetting procedure, for information on resetting a system shutdown.
Use the Alarm Off button to silence the alarm horn at the operator’s discretion.
If the controller is set up for an NFPA 110 application, press the AUTO button before silencing the alarm horn. The alarm horn
cannot be silenced unless the master control button is in the AUTO mode. See the section titled: Status and Notice Digital
Displays for more information.
Note:
Text shown in
italics
in this section of the manual represents digital display messages.
AC Sensing Loss.
The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the controller does not
detect the nominal generator set AC output voltage for more than 3 seconds after crank disconnect. The controller displays
AC
Sens Loss Shutdwn.
Alternator Protection.
The fault lamp illuminates red and the unit shuts down because of an alternator overload or short circuit.
The local display shows
Alt Protect
Shutdwn
. See Appendix titled: Alternator Protection for more information.
Auxiliary Input (Shutdown).
The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when an auxiliary
digital or analog inputs signals the controller. The digital inputs do not function during first the 30 seconds after startup. Use
SiteTech™ software to define inputs as shutdowns or warnings. The local display shows
Aux Input Shutdwn
.
Common Fault.
The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the controller is signaled
by a common fault. Use SiteTech™ software to activate the common fault shutdown. The local display shows
Common Fault
Shutdwn
. The common fault comprises the following shutdowns under a single alert.
Emergency stop
Engine over speed
High coolant temperature
Low oil pressure
Overcrank
ECM Address Conflict.
The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the controller
detects an error with the ECM address. The local display shows
ECMAddr Err Shutdwn.
ECM Communications Loss.
The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the ECM
communication link is disrupted. The local display shows
ECM Comm Err Shutdwn
.
ECM Diagnostics (Multiple Engine Inputs).
The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down
when ECM diagnostics signals the controller. The local display shows
ECM xxxxx Shutdwn
. The specific display (xxxxx) will be
a brief message or fault code that is engine manufacturer dependent. The engine literature provides the fault code description
and further information.
ECM Model Mismatch.
The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the controller
detects an error with the ECM model. The local display shows
ECM Mismatch Shutdwn
.
Emergency Stop.
The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the local or optional
remote emergency stop switch activates. The local display shows
Emerg Stop Shutdwn
.
Enclosure Temperature: High Shutdown (Available on select Telecom units only).
The fault lamp illuminates red, the alarm
horn sounds, and the unit shuts down when the enclosure reaches high temperature. The digital input does not function during
first the 20 seconds after startup and has a 5 second delay. The local display shows
Enclsr Temp: High Shutdwn
.
Engine Over Speed.
The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down immediately when the
governed frequency on 50 and 60 Hz models exceeds the over speed setting. The local display shows
Eng Speed High Shutdwn
.
Содержание APM402
Страница 6: ...6 TP 6694 9 20 ...
Страница 16: ...16 TP 6694 9 20 ...
Страница 42: ...42 TP 6694 9 20 ...
Страница 78: ...78 TP 6694 9 20 ...
Страница 112: ...112 TP 6694 9 20 ...
Страница 120: ...120 TP 6694 9 20 ...
Страница 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Страница 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Страница 126: ...126 TP 6694 9 20 Figure 56 60 IMS 300 kW Wound Exciter Field 20 300 kW 600 V Perm Magnet Alternators ADV 5875AB 3 ...
Страница 127: ...TP 6694 9 20 127 Figure 57 300 kW and Larger Pilot Excited Permanent Magnet 4M 5M 7M 10M Alternators ADV 5875AB 4 ...
Страница 128: ...128 TP 6694 9 20 ...
Страница 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Страница 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Страница 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Страница 171: ......